Refrigerant charging

How to add refrigerant

1.Connect manifold gauge to the gas side service valve.

2.Take the trial operation with the cooling trial operation mode.

3.Perform trial operation for longer than 10 minutes and add refrigerant based on the below pressure table.

❋❋Purpose of pressure table : If additional refrigerant filling is needed due to the leakage of the refrigerant or re-installation, add refrigerant using pressure table.

ENGLISH

Pressure table for temperatures (AP50M1AN✴✴✴) ffCooling operations

Pressure (Low pressure)

Outdoor temperature (°C)

[kPa, G]

 

21

35

43

 

21

370

430

450

 

23

390

450

480

Indoor

25

400

470

510

27

410

500

540

temperature(°C)

29

420

530

600

 

 

31

430

570

650

 

33

430

590

670

Pressure table for temperatures (AP50M0AN✴✴✴✴) ffCooling operations

Pressure (Low pressure)

Outdoor temperature (°C)

[kPa, G]

 

21

35

43

 

21

370

420

450

 

23

380

430

460

Indoor

25

390

440

470

27

390

460

490

temperature(°C)

29

410

480

510

 

 

31

420

500

540

 

 

 

 

 

4. Check the stability of the pressure for 10 minutes.

OUTDOOR UNIT

Gas side

Liquid side

5. After adding refrigerant, fasten cap nuts firmly.

• Always use R-22 refrigerant to avoid damage of the unit or an explosion.

CAUTION • Must keep the quantity of refrigerant by using a balance. Do not use a manometer or not depend on your experiences.

45

Mirage_AP50M0@_IBIM_EN_05323A-02.indd 45

2016-05-19 오후 1:27:27

Image 45
Contents Thank you for purchasing this Samsung product Air ConditionerFeatures of your new air conditioner Strong Turbo/Long FunctionLook for Everywhere Contents Safety precautions Important safety symbols and precautionsDo not yank the power cable with hands Ensure no water gets into the air conditioner FfPotential risk of injury or electric shock Use a rated circuit breaker onlyFfPotential risk of personal injury Do not open the front panel during operationDo not allow children to climb on the air conditioner FfInsufficient ventilation may result in poor performanceFfPotential risk of personal injury or property loss FfWearing thick gloves can protect your hands Checking the indoor unit and display Viewing your air conditionerMain parts To open the panelHeater and Purity function is not supported by this model Control panelRemote controller buttons Checking the remote controllerRemote controller display Using the remote controllerAre in the same space Storing the remote controller Battery changing timeInserting the batteries Indoor unitBasic operation Selecting the operation mode Turning on the powerAdjusting the desired temperature Selecting the fan speedSelecting air flow direction When the air conditioner is off Setting the On/Off timerYou cannot set the fan speed when setting the On timer Controller displayButton When the air conditioner is onWhen the air conditioner is operating in Cool or Heat mode Using the Turbo functionLocking the control panel Using the Long functionUsing the air conditioner with the control panel Cleaning and maintaining the air conditioner Cleaning the exteriorCleaning the filter Air filter Installation part Maintaining your air conditionerPeriodical checks Internal protections via the unit control system Have deposited at low temperaturesAppendix TroubleshootingHumidity Operation rangesOr accessing its internal components Installing the unitGeneral information PersonnelDo not install the air conditioner in following places Power supply line, fuse or circuit breakerMake sure that you earth the cables Complete, electric shock or fire may occurAccessory parts list Indoor unit Selection of installation placeTop view Side viewOutdoor unit Preparing the installation Selecting appropriate location for installationVentilate Wear protective goggles and mask before spraying Space requirementsElectrical work Wiring standardCord. Code designation IEC60245 IEC 66 / CENELECH07RN-F Ssc *2Indoor and outdoor connection wiring Using 4poles ELCBEarth Leakage Circuit BreakerAP50M0 Series AP50M1 Series Using 3poles Elcb and 2poles ElcbConnecting the power terminal Electrical wiringOutdoor unit When using the anchor bolt Installation methodWhen using the rubber leg Installation proceduresTrap Refrigerant pipe work Insulating the pipes Check the following list and install an oil trapOil trap FfRadius of curvature R on the oil trap are as followsConnection of refrigerant piping Flare processing Cut the pipe using the pipe cutterRemove burr on the edge of pipe It may cause explosion and injuryPipe bending Tightening of connection partsDrilling a hole in the wall Drain hose Wall installation Corner InstallationFixing the indoor unit ExampleBe sure that all valve cocks are closed Air purgeHow to add refrigerant Refrigerant chargingCheck the stability of the pressure for 10 minutes Check and test operation CheckIs grounding properly made? Pump down procedure When removing the product When the outdoor temperature is below zero, do notTest operation Packing and unpacking guide Outdoor unit Mm of the wire shields of the tube How to connect your extended power cablesPrepare the following tools TubeApply heat to the contraction tube to contract it FfMethodMirageAP50M0@IBIMEN05323A-02.indd 2016-05-19 오후 English Questions or COMMENTS?