Refrigerant charging
How to add refrigerant
1.Connect manifold gauge to the gas side service valve.
2.Take the trial operation with the cooling trial operation mode.
3.Perform trial operation for longer than 10 minutes and add refrigerant based on the below pressure table.
❋❋Purpose of pressure table : If additional refrigerant filling is needed due to the leakage of the refrigerant or
ENGLISH
Pressure table for temperatures (AP50M1AN✴✴✴) ffCooling operations
Pressure (Low pressure) | Outdoor temperature (°C) | ||||
[kPa, G] |
| 21 | 35 | 43 | |
| 21 | 370 | 430 | 450 | |
| 23 | 390 | 450 | 480 | |
Indoor | 25 | 400 | 470 | 510 | |
27 | 410 | 500 | 540 | ||
temperature(°C) | |||||
29 | 420 | 530 | 600 | ||
| |||||
| 31 | 430 | 570 | 650 | |
| 33 | 430 | 590 | 670 |
Pressure table for temperatures (AP50M0AN✴✴✴✴) ffCooling operations
Pressure (Low pressure) | Outdoor temperature (°C) | ||||
[kPa, G] |
| 21 | 35 | 43 | |
| 21 | 370 | 420 | 450 | |
| 23 | 380 | 430 | 460 | |
Indoor | 25 | 390 | 440 | 470 | |
27 | 390 | 460 | 490 | ||
temperature(°C) | |||||
29 | 410 | 480 | 510 | ||
| |||||
| 31 | 420 | 500 | 540 | |
|
|
|
|
|
4. Check the stability of the pressure for 10 minutes.
OUTDOOR UNIT
Gas side
Liquid side
5. After adding refrigerant, fasten cap nuts firmly.
• Always use
CAUTION • Must keep the quantity of refrigerant by using a balance. Do not use a manometer or not depend on your experiences.
45