Samsung AP50M1ANXSG, AP50M0ANXSG Installation method, Outdoor unit When using the anchor bolt

Page 38

Installation method

Outdoor unit

When using the anchor bolt

Fix the unit on a flat, rigid floor using the anchor bolt. (Anchor bolt : M10 x 4 points - separately purchased)

Anchor bolt fixing dimensions

670mm

403mm

427mm

When using the rubber leg

Put the rubber leg to the outdoor unit leg.

Outdoor unit leg

Rubber leg

Installation procedures

1.The piping of this unit can be connected to the right, left, and rear side.

-- When you hit the area for piping connection slightly with a hammer, a hole is made.

Holes for piping connection (4 points)

Protective piping cover

Piping

Drain hose

Protective piping cover

Drain hose

Piping

When the hole on the wall is lower than the hole for piping connection.

When the hole on the wall is higher than the hole for piping connection.

2.Open the front panel and separate it from the unit.

-- Be careful of the power lines connected to control panel when removing.

3.Bend the connection pipe to an appropriate length using the spring bender depending upon the installation place. -- Allowable pipe length : Maximum 25m

-- Allowable pipe drop distance : Maximum 15m

-- Make no more than ten bending points on the pipe

❋❋When the pipe length is in excess of the standard pipe length of 5m, add the refrigerant (R-22) of 40g for each additional 1m.

If the pipe is lengthened, the performance of the unit is degraded, and the service life is shortened. Therefore, the

CAUTION pipe length should be as short as possible (less than 25m).

38

Mirage_AP50M0@_IBIM_EN_05323A-02.indd 38

2016-05-19 오후 1:27:24

Image 38
Contents Air Conditioner Thank you for purchasing this Samsung productLook for Everywhere Features of your new air conditionerStrong Turbo/Long Function Contents Do not yank the power cable with hands Safety precautionsImportant safety symbols and precautions Ensure no water gets into the air conditioner FfPotential risk of personal injury Use a rated circuit breaker onlyFfPotential risk of injury or electric shock Do not open the front panel during operationFfPotential risk of personal injury or property loss Do not allow children to climb on the air conditionerFfInsufficient ventilation may result in poor performance FfWearing thick gloves can protect your hands Main parts Viewing your air conditionerChecking the indoor unit and display To open the panelControl panel Heater and Purity function is not supported by this modelChecking the remote controller Remote controller buttonsAre in the same space Remote controller displayUsing the remote controller Inserting the batteries Battery changing timeStoring the remote controller Indoor unitBasic operation Adjusting the desired temperature Turning on the powerSelecting the operation mode Selecting the fan speedSelecting air flow direction You cannot set the fan speed when setting the On timer Setting the On/Off timerWhen the air conditioner is off Controller displayWhen the air conditioner is on ButtonUsing the Turbo function When the air conditioner is operating in Cool or Heat modeUsing the Long function Locking the control panelUsing the air conditioner with the control panel Cleaning the filter Air filter Cleaning and maintaining the air conditionerCleaning the exterior Periodical checks Installation partMaintaining your air conditioner Have deposited at low temperatures Internal protections via the unit control systemTroubleshooting AppendixOperation ranges HumidityGeneral information Installing the unitOr accessing its internal components PersonnelMake sure that you earth the cables Power supply line, fuse or circuit breakerDo not install the air conditioner in following places Complete, electric shock or fire may occurAccessory parts list Top view Selection of installation placeIndoor unit Side viewOutdoor unit Ventilate Preparing the installationSelecting appropriate location for installation Space requirements Wear protective goggles and mask before sprayingCord. Code designation IEC60245 IEC 66 / CENELECH07RN-F Wiring standardElectrical work Ssc *2AP50M0 Series Indoor and outdoor connection wiringUsing 4poles ELCBEarth Leakage Circuit Breaker Using 3poles Elcb and 2poles Elcb AP50M1 SeriesElectrical wiring Connecting the power terminalWhen using the rubber leg Installation methodOutdoor unit When using the anchor bolt Installation proceduresTrap Oil trap Check the following list and install an oil trapRefrigerant pipe work Insulating the pipes FfRadius of curvature R on the oil trap are as followsRemove burr on the edge of pipe Cut the pipe using the pipe cutterConnection of refrigerant piping Flare processing It may cause explosion and injuryDrilling a hole in the wall Pipe bendingTightening of connection parts Fixing the indoor unit Wall installation Corner InstallationDrain hose ExampleAir purge Be sure that all valve cocks are closedCheck the stability of the pressure for 10 minutes How to add refrigerantRefrigerant charging Is grounding properly made? Check and test operationCheck Test operation Pump down procedure When removing the productWhen the outdoor temperature is below zero, do not Packing and unpacking guide Outdoor unit Prepare the following tools How to connect your extended power cablesMm of the wire shields of the tube TubeFfMethod Apply heat to the contraction tube to contract itMirageAP50M0@IBIMEN05323A-02.indd 2016-05-19 오후 English Questions or COMMENTS?