Power supply and wire specification
  | Model name  | 
  | 
  | 
  | 
  | Indoor unit  | 
  | Outdoor unit  | ||||||
  | 
  | 
  | 
  | 
  | AF80KV3SAEEN  | 
  | AF80KV3SAEEX  | |||||||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | ||
Power supply  | 
  | 
  | 
  | Product  | 
  | 
  | 220 - 240 V~ 50 Hz  | 380 - 415 V 3N~ 50 Hz  | ||||||
Power  | Cooling  | 
  | 
  | 
  | T1  | 
  | W  | 520 W  | 
  | 8000 W  | ||||
  | 
  | 
  | T3  | 
  | 
  | 520 W  | 
  | 7600 W  | ||||||
consumption  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | ||||||
Heating  | 
  | 
  | -  | 
  | 
  | 
  | W  | -  | 
  | -  | ||||
Operationg  | Cooling  | 
  | 
  | 
  | T1  | 
  | A  | 2.3 A  | 
  | 12.5 A  | ||||
  | 
  | 
  | T3  | 
  | 
  | 2.3 A  | 
  | 11.9 A  | ||||||
current  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | ||||||
Heating  | 
  | 
  | -  | 
  | 
  | 
  | A  | -  | 
  | -  | ||||
  | 
  | 
  | 
  | 
  | 
  | 
  | ||||||||
Capacity of  | 
  | Product  | 
  | 
  | 
  | A  | 30  | 
  | ||||||
circuit breaker  | 
  | 
  | 
  | 
  | 
  | |||||||||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
Thickness of ground wire  | 
  | 
  | 
  | mm2  | 4.0  | 
  | ||||||||
Indoor and outdoor unit  | 
  | 
  | 
  | mm2  | 0.75~1.5  | 
  | ||||||||
communication wire  | 
  | 
  | 
  | 
  | ||||||||||
  | 
  | 
  | 
  | 
  | 
  | 
  | ||||||||
  | 
  | 
  | 
  | 
  | Type  | 
  | 
  | 
  | 
  | At least equal to   | At least equal to   | |||
  | 
  | 
  | 
  | 
  | 
  | Below  | mm2  | 2.5 (Should be purchased  | 2.5 (Should be purchased  | |||||
Power wire  | Product  | 
  | 
  | 20m  | 
  | separately)  | 
  | separately)  | ||||||
  | 
  | 20m or  | mm2  | 4.0 (Should be purchased  | 4.0  | (Should be purchased  | ||||||||
  | 
  | 
  | 
  | 
  | 
  | |||||||||
  | 
  | 
  | 
  | 
  | 
  | 
  | over  | 
  | separately)  | 
  | separately)  | |||
  | Model name  | 
  | 
  | 
  | 
  | Indoor unit  | 
  | Outdoor unit  | ||||||
  | 
  | 
  | 
  | 
  | AF0AKV3SAEEN  | 
  | AF0AKV3SAEEX  | |||||||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | ||
Power supply  | 
  | 
  | 
  | 
  | Product  | 
  | 220 - 240 V~ 50 Hz  | 380 - 415 V 3N~ 50 Hz  | ||||||
  | 
  | 
  | Cooling  | 
  | 
  | T1  | W  | 560 W  | 
  | 11 900 W  | ||||
Power consumption  | 
  | 
  | 
  | T3  | 560 W  | 
  | 9900 W  | |||||||
  | 
  | 
  | Heating  | 
  | 
  | -  | W  | -  | 
  | -  | ||||
  | 
  | 
  | Cooling  | 
  | 
  | T1  | A  | 2.5 A  | 
  | 18.3 A  | ||||
Operationg current  | 
  | 
  | 
  | T3  | 2.5 A  | 
  | 15.4 A  | |||||||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |||||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |||
  | 
  | 
  | Heating  | 
  | 
  | -  | A  | -  | 
  | -  | ||||
Capacity of circuit  | 
  | 
  | 
  | Product  | 
  | A  | 30  | 
  | ||||||
breaker  | 
  | 
  | 
  | 
  | 
  | 
  | ||||||||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
Thickness of ground wire  | 
  | 
  | 
  | mm2  | 4.0  | 
  | ||||||||
Indoor and outdoor unit  | 
  | 
  | 
  | mm2  | 0.75~1.5  | 
  | ||||||||
communication wire  | 
  | 
  | 
  | 
  | ||||||||||
  | 
  | 
  | 
  | 
  | 
  | 
  | ||||||||
  | 
  | 
  | 
  | 
  | 
  | Type  | 
  | 
  | At least equal to   | At least equal to   | ||||
  | 
  | 
  | 
  | 
  | 
  | 
  | Below  | mm2  | 2.5 (Should be purchased  | 4.0 (Should be purchased  | ||||
Power wire  | Product  | 
  | 20m  | separately)  | 
  | separately)  | ||||||||
  | 
  | 
  | 20m  | mm2  | 4.0 (Should be purchased  | 6.0  | (Should be purchased  | |||||||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |||||||
  | 
  | 
  | 
  | 
  | 
  | 
  | or over  | 
  | separately)  | 
  | separately)  | |||
INSTALLATION PARTS
English 57