Wiring work
Selecting solderless ring terminal
•Select a compressed ring terminal of a power cable based on a nominal dimensions for cable.
•Cover a compressed ring terminal and a connector part of the power cable and then connect it.
Silver solder
INSTALLATION PARTS
Nominal dimensions for cable (mm2) | 4/6 | 10 | 16 | 25 | 35 | 50 | 70 | ||||||||
Nominal dimensions for screw (mm) | 4 |
| 8 | 8 | 8 | 8 |
| 8 | 8 |
| 8 | 8 | 8 | ||
B | Standard dimension (mm) | 9.5 |
| 15 | 15 | 16 | 12 |
| 16.5 | 16 |
| 22 | 22 | 24 | |
Allowance (mm) | ±0.2 | ±0.2 | ±0.2 | ±0.3 | ±0.3 | ±0.3 | ±0.4 | ||||||||
| |||||||||||||||
| Standard dimension (mm) | 5.6 | 7.1 | 9 | 11.5 | 13.3 | 13.5 | 17.5 | |||||||
D | Allowance (mm) | +0.3 | +0.3 | +0.3 | +0.5 | +0.5 | +0.5 | +0.5 | |||||||
| |||||||||||||||
|
| ||||||||||||||
d1 | Standard dimension (mm) | 3.4 | 4.5 | 5.8 | 7.7 | 9.4 | 11.4 | 13.3 | |||||||
Allowance (mm) | ±0.2 | ±0.2 | ±0.2 | ±0.2 | ±0.2 | ±0.3 | ±0.4 | ||||||||
| |||||||||||||||
E | Min. |
| 6 | 7.9 | 9.5 | 11 | 12.5 | 17.5 | 18.5 | ||||||
F | Min. | 5 |
| 9 | 9 | 13 | 15 |
| 13 | 13 |
| 13 | 14 | 20 | |
L | Max. | 20 |
| 28.5 | 30 | 33 | 34 | 38 |
| 43 | 50 | 51 | |||
| Standard dimension (mm) | 4.3 |
| 8.4 | 8.4 | 8.4 | 8.4 |
| 8.4 | 8.4 |
| 8.4 | 8.4 | 8.4 | |
d2 | Allowance (mm) | + 0.2 | +0.4 | +0.4 | +0.4 | +0.4 | +0.4 | +0.4 | +0.4 | ||||||
| 0 |
| 0 | 0 | 0 |
| 0 |
| 0 | 0 | 0 | ||||
|
|
|
|
| |||||||||||
t | Min. | 0.9 | 1.15 | 1.45 | 1.7 | 1.8 | 1.8 | 2.0 |
60English