INSTALLATION PARTS
Troubleshooting
The table below give indication about self diagnostic routine. Some of error code requires activities exclusively for Authorized Service Center.
Outdoor unit
If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER PCB.
No. | Error | Meaning | Remarks | |
Code | ||||
|
| Error due to repeated address setting(when 2 | Check on repeated indoor unit main | |
1 | E108 | or more devices has same address within the | ||
address | ||||
|
| network) | ||
|
|
| ||
2 | E121 | Error on indoor temperature sensor of indoor | Indoor unit Room Thermistor Open/ | |
unit(Short or Open) | Short | |||
3 | E122 | Error on EVA IN sensor of indoor unit(Short or | Indoor unit EVA_IN Thermistor Open/ | |
Open) | Short | |||
4 | E123 | Error on EVA OUT sensor of indoor unit(Short or | Indoor unit EVA_OUT Thermistor | |
Open) | Open/Short | |||
5 | E153 | Error on float switch (2nd detection) | "Indoor unit Float Switch Open/Short | |
Drain Pump operation Check" | ||||
|
|
| ||
6 | E154 | RPM feedback error of indoor unit | Check on indoor unit indoor Fan | |
operation | ||||
|
|
| ||
7 | E162 | Outdoor unit EEPROM Read/Write error (H/W) | Check Outdoor EEPROM PBA | |
8 | E163 | Outdoor unit EEPROM Read/Write error (Option) | Check Outdoor EEPROM Data | |
9 | E198 | Error on thermal fuse of indoor unit (Open) | Thermal Fuse Open Check of indoor | |
unit Terminal Block | ||||
|
|
| ||
|
| "Communication error between indoor and |
| |
10 | E201 | outdoor unit(Installation number setting error | Check indoor quantity setting in | |
repeated indoor unit address,indoor unit | outdoor | |||
|
| communication cable error)" |
| |
|
| "Communication error between indoor and | Check electrical connection and setting | |
11 | E202 | outdoor unit(Communication error on all indoor | ||
between indoor unit and outdoor unit | ||||
|
| unit, outdoor unit communication cable error)" |
| |
12 | E205 | Communication error on all PBA within the | - | |
outdoor unit | ||||
13 | E206 | - | ||
14 | E221 | Error on outdoor temperature sensor (Short or | Check Outdoor sensor Open / Short | |
Open) | ||||
15 | E231 | Error on outdoor COND OUT sensor (Short or | Check | |
Open) |