Refrigerant piping work
Pipe connection
Indoor unit  | Outdoor unit  | 
Gas pipe![]()
![]()
Liquid pipe ![]()
Gas  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | Liquid  | |
pipe  | 
  | 
  | 
  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | pipe  | |
  | 
  | 
  | 
  | 
  | 
  | 
Selecting refrigerant pipe
  | Model name  | Liquid side (mm)  | Gas side (mm)  | |
  | AF80KV3SAEEX  | Ø9.52  | Ø19.05  | |
  | AF0AKV3SAEEX  | Ø9.52  | Ø22.23  | |
  | Temper grade and minimum thickness of the refrigerant pipe | |||
  | 
  | 
  | 
  | |
  | Outer diameter [mm/(inch)]  | Minimum thickness (mm)  | Temper grade  | |
  | Ø 6.35 (1/4)  | 0.7  | 
  | |
INSTALLATION  | Ø 9.52 (3/8)  | 0.7  | 
  | |
Ø 25.40 (1)  | 1.0  | 
  | ||
  | Ø 12.70 (1/2)  | 0.8  | ||
  | Ø 15.88 (5/8)  | 0.8  | 
  | |
  | Ø 19.05 (3/4)  | 1.0  | 
  | |
  | Ø 22.23 (7/8)  | 0.9  | 
  | |
PARTS  | 
  | 
  | 
  | |
Ø 28.58   | 1.1  | |||
  | ||||
  | Ø 31.75   | 1.1  | ||
  | ||||
  | Ø 38.10   | 1.35  | ||
  | 
  | |||
  | Ø 44.45   | 1.6  | 
  | |
  | Ø 50.80 (2)  | 2.0  | 
  | |
48English