Napoleon Fireplaces BGD42CFN, BGD36CFGN, BGD36CFNTR BGD36CFG Rear Exit / Horizontal Termination

Page 13

13

BGD36CF(G) REAR EXIT / HORIZONTAL TERMINATION

when (HT) < (VT)

Simple venting confi guration (only two 90° elbows)

FIGURE 25

See graph to determine the required vertical rise VT for the required horizontal run HT

REQUIRED VER-

TICAL RISE IN

FEET

VT

HORIZONTAL VENT RUN PLUS OFF-

SETS IN FEET HT

The shaded area within the lines represents acceptable values for HT and VT .

For vent confi gurations requiring more than two 90° elbows the fol- lowing formulas apply:

Formula 1: HT < VT

90°

Formula 2: HT + VT < 40 feet

H3

90°V2

when (HT) > (VT)

Simple venting confi guration (only two 90° elbows)

FIGURE 27

See graph to determine the required vertical rise VT for the required horizontal run HT

REQUIRED VERTICAL

RISE IN INCHES VT

HORIZONTAL VENT RUN

PLUS OFFSETS IN FEET HT

The shaded area within the lines represents acceptable values for HT and VT .

For vent confi gurations requiring more than two 90° elbows the fol- lowing formulas apply:

Formula 1: HT < 3.5VT

90°

Formula 2: HT + VT < 24.75 feet

H4

H2

FIGURE 26

Example 5:

90°

V

 

 

 

45°

2

90°

V1

H1 90°

Example 4:

V1 = 9 ft V2 = 6 ft

VT = V1 + V2 = 9 + 6 = 15 ft H1 = 3 ft

H2 = 2 ft H3 = 1.5 ft

HR = H1 + H2 + H3 = 3 + 2 + 1.5 = 6.5 ft HO = .03 (four 90° elbows - 90°)

= .03(90 + 90 + 90 + 90 - 90) = 8.1 ft

HT = HR + HO = 6.5 + 8.1 = 14.6 ft

HT + VT = 14.6 + 15 = 29.6 ft

Formula 1: HT < VT 14.6 < 15

Formula 2: HT + VT < 40 feet 29.6 < 40

Since both formulas are met, this vent confi guration is ac- ceptable.

H2

90°

V1

H3

 

H1

FIGURE 28

 

90°

V1=4 ft V2=1.5 ft

VT=V1 + V2 = 4 + 1.5 = 5.5 ft H1=2 ft

H2=1 ft H3=1 ft H4=1.5 ft

HR=H1 + H2 + H3 + H4 = 2 + 1 + 1 + 1.5 = 5.5 ft HO=.03 (four 90° elbows + one 45° elbow - 90°)

=.03(90 + 90 + 90 + 90 + 45 - 90) = 9.45 ft HT=HR + HO = 5.5 + 9.45 = 14.95 ft

HT + VT= 14.95 + 5.5 = 20.45 ft

Formula 1: HT < 3.5VT

3.5VT = 3.5 x 5.5 = 19.25 ft

14.95< 19.25

Formula 2: HT + VT < 24.75 feet

20.45< 24.75

Since both formulas are met, this vent confi guration is ac- ceptable.

W415-0661 / C / 02.20.08

Image 13
Contents Installation Operating Instructions Table of Contents W415-0661 / C General Information General InstructionsCare of Glass and Plated Parts For example in Massachusetts StateInstallation Overview Unit Dimensions38 1/2 24 1/4Venting Lengths VentingW415-0661 / C See Venting Section Typical Minimum and Maximum Vent LengthsTOP Exit Installation Rear Exit Installation Special Vent InstallationsPeriscope Termination Corner TerminationFireplace Vent Exit Rear Exit TOP Exit Venting Application Flow ChartHorizontal Termination Vertical Termination BGD36CFG TOP Exit / Horizontal Termination When HT VTDefinitions Elbow Vent Length ValuesFormula 2 HT + VT 24.75 feet ExampleFormula 1 HT VT Formula 2 HT + VT 40 feet BGD36CFG Rear Exit / Horizontal TerminationFormula 1 HT 3.5VT Formula 2 HT + VT 24.75 feet Example Formula 1 HT 3VT Formula 2 HT + VT 40 feet Example Formula 2 HT + VT 40 feet Example =5 ftBGD36CFG TOP or Rear Exit Vertical Termination BGD42CF Horizontal Termination = .03 45 + 90 + 90 +90 135 = 5.4 ft BGD42CF Vertical Termination= HR + HO = 5.5 + 5.4 = 10.9 ft HT + VTFormula 1 HT 3VT Formula 2 HT + VT 40 feet Example Installation Wall and Ceiling Protection BGD36CFG PRE-INSTALLATION PreparationBGD42CF only Adjustable Firestop Installation Vertical InstallationSpace around the pipe. Nail Headers between the joist forHorizontal AIR Terminal Installation Using Flexible Vent ComponentsVertical Venting Installation Using Rigid Vent ComponentsExtended Horizontal and Corner AIR Terminal Installation Mobile Home Installation GAS InstallationOptional Wall Switch Installation Excluding BGD36CFG Restricting Vertical VentsFraming Installing StandoffsCavity 46 1/2 BGD36CFG BGD42CFBGD36CFG Minimum Mantel and Enclosure Clearances Finished Floor Installation Clean Face Surround Minimum Enclosure ClearancesConvex Concave Optional Clean Face Trim KIT Installation Hearth Installation37 3 BGD42CF Minimum Mantel and Enclosure Clearances Door Installation / Removal LOG PlacementGLASS/DOOR Replacement Finishing BGD36CF FinishingGrate Installation Door Trim LOG PlacementGrate BGD36CFG Finishing BGD42CF Accessing the Blower Optional Blower InstallationInstalling the Blower BGD36CFG Accessing the Blower FigureElectrical Code in the United States GD36 Thermostatic Sensor ControlGauge Feet BGD36CFG Burner Switch / Wiring DiagramBGD36CFG Light Switch / Wiring Diagram Receptacle Wiring Diagram Lighting Instructions Operation BGD36CF & BGD42CFTo Turn OFF GAS For Your Safety Read Before Operating MaintenanceOperation BGD36CFG Operating InstructionsVenturi Adjustment AdjustmentsBGD36CFG Venturi Adjustment Pilot Burner Adjustment Excluding BGD36CFGBGD36CF Flame Characteristics Flame AdjustmentBGD42CF Flame Characteristics BGD36CFG Flame CharacteristicsBGD36CFG Replacements Common ReplacementsBGD42CF Replacements W415-0661 / C Symptom Problem Test Solution BGD36CFG Trouble Shooting GuideRight order Pilot lights Wiring / ConnectionNot turn on Module or Valve Ing, touch black lead to ground valve bodyAn interlock device Gas valve hasWhich will not allow Pilot burner to be Lit until the thermoModel BGD42CF only