Napoleon Fireplaces BGD42CFN, BGD36CFGN, BGD36CFNTR manual BGD36CFG PRE-INSTALLATION Preparation

Page 19

19

BGD36CF(G) PRE-INSTALLATION PREPARATION

(THIS PROCEDURE IS NOT REQUIRED FOR THE BGD42CF)

For optimum performance, it is recommended that all horizontal runs have a 1" rise per foot.

REMOVING THE VALVE ACCESS DOOR

1.The valve access door rotates on the pins attached to the side frame. Lift the valve access door off the pins to operate

the main glass door.

FIGURE 43

Do not over tighten. The gasket FIGURE 45 needs only to be snug against the

rebox. FIGURE 45.

TOP EXIT:

DOOR OPERATION

To access the lower door latch,

FIGURE 44open the Valve Access

Door as illustrated. Release the top and bottom door latches, located at the right side of the door.

1. Remove the 7" diameter capFIGURE 46 from the top of the fireplace and re-

secure it over the 7" collar located at the rear of the unit. Press fi rmly on the cap while securing to ensure an airtight seal. Do not damage the gasket.

!

REAR EXIT:

Before attaching elbows to the collars on the back of the fireplace, 1½" will need to be trimmed off the 4" collar.

From inside the fi rebox, insert the 4" fl ue pipe / gasket assembly (provided) through the rear of the fi rebox.

Secure the gasket assembly to the rear and top of the unit using 4 #8 x 3/4" Hex Head Wildrill screws supplied.

FAILURE TO INSTALL THE CAP WILL CAUSE THE FIRE- PLACE TO FUNCTION IMPROPERLY AND CAN CAUSE INJURY OR PROPERTY DAMAGE.

2.Remove the plate covering the 4" diameter flue opening (seen inside the top of the 7" diameter collar) and discard. Try not to disturb the retaining ring or the gasket beneath. Re-secure the ring and gasket using the screws removed from the plate.

3.From inside the firebox, insert the 4" flue pipe assembly through the heat shield and out through the retaining ring. Secure the assembly to the rear and top of the unit using 4 #8 x ¾" Hex Head Wildrill screws supplied. Do not over tighten. The gasket needs only to be snug against the fi rebox. FIGURE 46.

INSTALLATION

WALL AND CEILING PROTECTION

BGD36CF(G)

 

BGD36CF(G) ONLY

HORIZONTAL VENT SECTIONS: - A minimum clearance of 1" at the bottom and sides of the vent and 2" at the top on all horizontal runs to combustibles is required. The fi restop spacer (W010-1774) supplied with the unit must be used to maintain this clearance.

VERTICAL VENT SECTIONS: - A minimum of 1" all around the vent pipe on all vertical runs to combustibles is required except for clear- ances in fireplace enclosures. See "MINIMUM ENCLOSURE CLEAR- ANCES" section. Use fi restop spacer W500-0096 (not supplied).

BGD42CF

HORIZONTAL VENT SECTIONS: A minimum clearance of 2" all around the vent pipe on all horizontal runs to combustibles is required. Use fi restop spacer W010-1778 (supplied).

VERTICAL VENT SECTIONS: A minimum of 1" all around the vent pipe on all vertical runs to combustibles is required. Use firestop spacer W500-0028 (not supplied).

HORIZONTAL INSTALLATION

FIGURE 47 BGD36CF(G)

BGD42CF

11 3/8

9 7/8”

16 1/4

14 7/16”

RECTANGULAR

RECTANGULAR

 

HOLE

 

HOLE

This application occurs when venting through an exterior wall.

Having determined the correct height for the air terminal location, cut and frame a hole in the exterior wall 9 7/8" wide by 11 3/8" high to accommodate the firestop assembly. Dry fit the firestop assembly before proceeding to ensure the brackets on the rear surface fit within the horizontal framing.

As an alternative to framing, the vent pipe can be enclosed in the wall using Napoleon® vent sleeve VS47KT.

NOTE: THE FIRESTOP ASSEMBLY MUST BE INSTALLED WITH THE VENT SHIELD TO THE TOP.

The length of the vent shield may be cut shorter for combustible walls that are less than 8 1/2" thick but the vent shield must extend the full depth of the combustible wall.

1.Apply a bead of caulking (not supplied) around the outer edge of the inside surface of the firestop assembly, fit the firestop assembly to the hole and secure using the 4 screws (W415-0026) supplied in your manual baggy.

2.Once the vent pipe is installed in its final position, apply high temperature sealant W573-0002 (not supplied) between the pipe, and the fi restop.

NOTE: DO NOT FILL THE CAVITY BETWEEN THE VENT PIPE AND THE FIRESTOP SLEEVE WITH ANY TYPE OF MATERIAL.

W415-0661 / C / 02.20.08

Image 19
Contents Installation Operating Instructions Table of Contents W415-0661 / C For example in Massachusetts State General InstructionsGeneral Information Care of Glass and Plated Parts24 1/4 Unit DimensionsInstallation Overview 38 1/2Venting Lengths VentingW415-0661 / C See Venting Section Typical Minimum and Maximum Vent LengthsCorner Termination Special Vent InstallationsTOP Exit Installation Rear Exit Installation Periscope TerminationFireplace Vent Exit Rear Exit TOP Exit Venting Application Flow ChartHorizontal Termination Vertical Termination Elbow Vent Length Values When HT VTBGD36CFG TOP Exit / Horizontal Termination DefinitionsFormula 2 HT + VT 24.75 feet ExampleFormula 1 HT VT Formula 2 HT + VT 40 feet BGD36CFG Rear Exit / Horizontal TerminationFormula 1 HT 3.5VT Formula 2 HT + VT 24.75 feet Example Formula 1 HT 3VT Formula 2 HT + VT 40 feet Example Formula 2 HT + VT 40 feet Example =5 ftBGD36CFG TOP or Rear Exit Vertical Termination BGD42CF Horizontal Termination HT + VT BGD42CF Vertical Termination= .03 45 + 90 + 90 +90 135 = 5.4 ft = HR + HO = 5.5 + 5.4 = 10.9 ftFormula 1 HT 3VT Formula 2 HT + VT 40 feet Example Installation Wall and Ceiling Protection BGD36CFG PRE-INSTALLATION PreparationHeaders between the joist for Vertical InstallationBGD42CF only Adjustable Firestop Installation Space around the pipe. NailHorizontal AIR Terminal Installation Using Flexible Vent ComponentsVertical Venting Installation Using Rigid Vent ComponentsExtended Horizontal and Corner AIR Terminal Installation Restricting Vertical Vents GAS InstallationMobile Home Installation Optional Wall Switch Installation Excluding BGD36CFGFraming Installing StandoffsCavity 46 1/2 BGD36CFG BGD42CFBGD36CFG Minimum Mantel and Enclosure Clearances Finished Floor Installation Clean Face Surround Minimum Enclosure ClearancesConvex Concave Optional Clean Face Trim KIT Installation Hearth Installation37 3 BGD42CF Minimum Mantel and Enclosure Clearances Finishing BGD36CF Finishing LOG PlacementDoor Installation / Removal GLASS/DOOR ReplacementGrate Installation Door Trim LOG PlacementGrate BGD36CFG Finishing BGD36CFG Accessing the Blower Figure Optional Blower InstallationBGD42CF Accessing the Blower Installing the BlowerElectrical Code in the United States GD36 Thermostatic Sensor ControlGauge Feet BGD36CFG Burner Switch / Wiring DiagramBGD36CFG Light Switch / Wiring Diagram Receptacle Wiring Diagram Lighting Instructions Operation BGD36CF & BGD42CFTo Turn OFF GAS Operating Instructions MaintenanceFor Your Safety Read Before Operating Operation BGD36CFGPilot Burner Adjustment Excluding BGD36CFG AdjustmentsVenturi Adjustment BGD36CFG Venturi AdjustmentBGD36CFG Flame Characteristics Flame AdjustmentBGD36CF Flame Characteristics BGD42CF Flame CharacteristicsBGD36CFG Replacements Common ReplacementsBGD42CF Replacements W415-0661 / C Symptom Problem Test Solution BGD36CFG Trouble Shooting GuideIng, touch black lead to ground valve body Pilot lights Wiring / ConnectionRight order Not turn on Module or ValveLit until the thermo Gas valve hasAn interlock device Which will not allow Pilot burner to beModel BGD42CF only