Napoleon Fireplaces BGD36CFNTR, BGD36CFGN BGD36CFG TOP Exit / Horizontal Termination, Definitions

Page 11

DEFINITIONS

for the following symbols used in the venting calculations and examples are:

>- greater than

>- equal to or greater than

<- less than

<- equal to or less than

HT - total of both horizontal vent lengths (HR) and offsets (HO) in feet

HR - combined horizontal vent lengths in feet

HO - offset factor: .03 (total degrees of offset - 90°*) in feet

VT - combined vertical vent lengths in feet

11

ELBOW VENT LENGTH VALUES

 

feet

inches

0.03

0.5

15°

0.45

6.0

30°

0.9

11.0

45°*

1.35

16.0

90°*

2.7

32.0

*BGD36CF the fi rst 90° offset has a zero value and is shown in the formula as - 90°

*BGD42CF the fi rst 45° and 90° offset has a zero value and

is shown in the formula as -45° and - 90° respectively or -135°

combined.

BGD36CF(G) TOP EXIT / HORIZONTAL TERMINATION

when (HT) < (VT)

Simple venting confi guration (only one 90° elbow)

See graph to determine the required vertical rise VT for the required horizontal run HT.

FIGURE 20

Formula 1: HT < VT

Formula 2: HT + VT < 40 feet

Example 1:

90° H2

V2

For vent configurations requiring more than one 90° elbow, the following formulas apply:

V E R T I C A L

RISE IN FEET

VT

90°

H1

90°

V1

FIGURE 21

HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT

The shaded area within the lines represents acceptable values for HT and VT .

V1 = 3 ft V2 = 8 ft

VT = V1 + V2 = 3 + 8 = 11 ft H1 = 2.5 ft

H2 = 2 ft

HR = H1 + H2 = 2.5 + 2 = 4.5 ft

HO = .03 (three 90° elbows - 90°) = .03(270° - 90°) = 5.4 ft HT = HR + HO = 4.5 + 5.4 = 9.9 ft

HT + VT = 9.9 + 11 = 20.9 ft

Formula 1: HT < VT 9.9 < 11

Formula 2: HT + VT < 40 feet 20.9 < 40

Since both formulas are met, this vent confi guration is ac- ceptable.

W415-0661 / C / 02.20.08

Image 11
Contents Installation Operating Instructions Table of Contents W415-0661 / C For example in Massachusetts State General InstructionsGeneral Information Care of Glass and Plated Parts24 1/4 Unit DimensionsInstallation Overview 38 1/2Venting Lengths VentingW415-0661 / C See Venting Section Typical Minimum and Maximum Vent LengthsCorner Termination Special Vent InstallationsTOP Exit Installation Rear Exit Installation Periscope TerminationHorizontal Termination Vertical Termination Venting Application Flow ChartFireplace Vent Exit Rear Exit TOP Exit Elbow Vent Length Values When HT VTBGD36CFG TOP Exit / Horizontal Termination DefinitionsFormula 2 HT + VT 24.75 feet ExampleFormula 1 HT 3.5VT Formula 2 HT + VT 24.75 feet Example BGD36CFG Rear Exit / Horizontal TerminationFormula 1 HT VT Formula 2 HT + VT 40 feet Formula 1 HT 3VT Formula 2 HT + VT 40 feet Example Formula 2 HT + VT 40 feet Example =5 ftBGD36CFG TOP or Rear Exit Vertical Termination BGD42CF Horizontal Termination HT + VT BGD42CF Vertical Termination= .03 45 + 90 + 90 +90 135 = 5.4 ft = HR + HO = 5.5 + 5.4 = 10.9 ftFormula 1 HT 3VT Formula 2 HT + VT 40 feet Example Installation Wall and Ceiling Protection BGD36CFG PRE-INSTALLATION PreparationHeaders between the joist for Vertical InstallationBGD42CF only Adjustable Firestop Installation Space around the pipe. NailHorizontal AIR Terminal Installation Using Flexible Vent ComponentsExtended Horizontal and Corner AIR Terminal Installation Using Rigid Vent ComponentsVertical Venting Installation Restricting Vertical Vents GAS InstallationMobile Home Installation Optional Wall Switch Installation Excluding BGD36CFGCavity Installing StandoffsFraming 46 1/2 BGD36CFG BGD42CFBGD36CFG Minimum Mantel and Enclosure Clearances Convex Concave Clean Face Surround Minimum Enclosure ClearancesFinished Floor Installation 37 3 Hearth InstallationOptional Clean Face Trim KIT Installation BGD42CF Minimum Mantel and Enclosure Clearances Finishing BGD36CF Finishing LOG PlacementDoor Installation / Removal GLASS/DOOR ReplacementGrate Door Trim LOG PlacementGrate Installation BGD36CFG Finishing BGD36CFG Accessing the Blower Figure Optional Blower InstallationBGD42CF Accessing the Blower Installing the BlowerElectrical Code in the United States GD36 Thermostatic Sensor ControlGauge Feet BGD36CFG Burner Switch / Wiring DiagramBGD36CFG Light Switch / Wiring Diagram Receptacle Wiring Diagram To Turn OFF GAS Operation BGD36CF & BGD42CFLighting Instructions Operating Instructions MaintenanceFor Your Safety Read Before Operating Operation BGD36CFGPilot Burner Adjustment Excluding BGD36CFG AdjustmentsVenturi Adjustment BGD36CFG Venturi AdjustmentBGD36CFG Flame Characteristics Flame AdjustmentBGD36CF Flame Characteristics BGD42CF Flame CharacteristicsBGD36CFG Replacements Common ReplacementsBGD42CF Replacements W415-0661 / C Symptom Problem Test Solution BGD36CFG Trouble Shooting GuideIng, touch black lead to ground valve body Pilot lights Wiring / ConnectionRight order Not turn on Module or ValveLit until the thermo Gas valve hasAn interlock device Which will not allow Pilot burner to beModel BGD42CF only