Napoleon Fireplaces BGD36CFNTR, BGD36CFGN manual Vertical Installation, Space around the pipe. Nail

Page 20

20

FIGURE 48

BGD42CF ONLY

ADJUSTABLE FIRESTOP INSTALLATION

Apply a bead of caulking all around the edge of the opening and place the fi restop top, so that the vent shield covers the top of the vent within the opening.

The length of the vent shield may be cut shorter for combustible walls that are less than 8 1/2" thick but the vent shield must extend the full depth of the combustible wall.

Place the fi restop bottom against the fi restop top and secure the two together. Adjust the assembly to ensure it is tight to the vent. Secure fi restop to wall. Ensure that both spacer and shield main- tain the required clearance to combustibles. Once the vent pipe is installed in its fi nal position, apply sealant between the vent pipe and the fi restop spacer. This restricts cold air from being drawn into the room or around the fi replace. See Figures 49a-c.

VENT SHIELD

FIGURE 49a

FIRESTOP TOP

FIRESTOP BOTTOM

FIGURE 49b

FIGURE 49c

Where the opening in the outside wall has been cut 13" tall to provide 2" clearance from the vent pipe, terminal extension plate W500-0206 must be used to cover the opening.

VERTICAL INSTALLATION

1.Determine the air terminal location, cut and frame 9 3/4" for the BGD36CF(G), or 10 3/4" for the BGD42CF square opening in the ceiling and an opening in the roof to provide the minimum 1" clearance between the fi replace vent pipe and any combustible material. Try to center the exhaust pipe location midway between two joists to prevent having to cut them. Use a plumb bob to line up the center of the openings.

DO NOT FILL THIS SPACE WITH ANY TYPE OF MATERIAL.

A vent pipe shield will prevent

 

any materials such as insula-

 

tion, from fi lling up the 1" air

BGD36CF(G) = 9 3/4”

space around the pipe. Nail

headers between the joist for

BGD42CF = 10 3/4”

extra support.

 

2.Apply a bead of caulking

(not supplied) to the frame- work or to the Wolf Steel vent pipe shield plate or equivalent (in the case of a fi nished

FIGURE 50

ceiling), and secure over the opening in the ceiling. A

restop must be placed on the bottom of each framed opening in a roof or ceiling that the venting system passes through.

Apply a bead of caulking all

around and place a fi restop

spacer over the vent shield toFIGURE 51 restrict cold air from being drawn

into the room or around the fi replace. Ensure that both spacer and shield maintain the required clearance to combustibles. Once the vent pipe is installed in its fi nal

position, apply high temperature sealant W573-0002 (not sup- plied) between the vent pipe and the fi restop spacer.

3.In the attic, slide the vent pipe collar down to cover up the open end of the shield and tighten.

This will prevent any materials, such as insulation, from fi lling up the 1" air space around the pipe.

FIGURE 52

W415-0661 / C / 02.20.08

Image 20
Contents Installation Operating Instructions Table of Contents W415-0661 / C General Instructions General InformationCare of Glass and Plated Parts For example in Massachusetts StateUnit Dimensions Installation Overview38 1/2 24 1/4Venting Venting LengthsW415-0661 / C Typical Minimum and Maximum Vent Lengths See Venting SectionSpecial Vent Installations TOP Exit Installation Rear Exit InstallationPeriscope Termination Corner TerminationHorizontal Termination Vertical Termination Venting Application Flow ChartFireplace Vent Exit Rear Exit TOP Exit When HT VT BGD36CFG TOP Exit / Horizontal TerminationDefinitions Elbow Vent Length ValuesExample Formula 2 HT + VT 24.75 feetFormula 1 HT 3.5VT Formula 2 HT + VT 24.75 feet Example BGD36CFG Rear Exit / Horizontal TerminationFormula 1 HT VT Formula 2 HT + VT 40 feet Formula 2 HT + VT 40 feet Example =5 ft Formula 1 HT 3VT Formula 2 HT + VT 40 feet ExampleBGD36CFG TOP or Rear Exit Vertical Termination BGD42CF Horizontal Termination BGD42CF Vertical Termination = .03 45 + 90 + 90 +90 135 = 5.4 ft= HR + HO = 5.5 + 5.4 = 10.9 ft HT + VTFormula 1 HT 3VT Formula 2 HT + VT 40 feet Example BGD36CFG PRE-INSTALLATION Preparation Installation Wall and Ceiling ProtectionVertical Installation BGD42CF only Adjustable Firestop InstallationSpace around the pipe. Nail Headers between the joist forUsing Flexible Vent Components Horizontal AIR Terminal InstallationExtended Horizontal and Corner AIR Terminal Installation Using Rigid Vent ComponentsVertical Venting Installation GAS Installation Mobile Home InstallationOptional Wall Switch Installation Excluding BGD36CFG Restricting Vertical VentsCavity Installing StandoffsFraming BGD36CFG BGD42CF 46 1/2BGD36CFG Minimum Mantel and Enclosure Clearances Convex Concave Clean Face Surround Minimum Enclosure ClearancesFinished Floor Installation 37 3 Hearth InstallationOptional Clean Face Trim KIT Installation BGD42CF Minimum Mantel and Enclosure Clearances LOG Placement Door Installation / RemovalGLASS/DOOR Replacement Finishing BGD36CF FinishingGrate Door Trim LOG PlacementGrate Installation BGD36CFG Finishing Optional Blower Installation BGD42CF Accessing the BlowerInstalling the Blower BGD36CFG Accessing the Blower FigureGD36 Thermostatic Sensor Control Electrical Code in the United StatesBGD36CFG Burner Switch / Wiring Diagram Gauge FeetBGD36CFG Light Switch / Wiring Diagram Receptacle Wiring Diagram To Turn OFF GAS Operation BGD36CF & BGD42CFLighting Instructions Maintenance For Your Safety Read Before OperatingOperation BGD36CFG Operating InstructionsAdjustments Venturi AdjustmentBGD36CFG Venturi Adjustment Pilot Burner Adjustment Excluding BGD36CFGFlame Adjustment BGD36CF Flame CharacteristicsBGD42CF Flame Characteristics BGD36CFG Flame CharacteristicsCommon Replacements BGD36CFG ReplacementsBGD42CF Replacements W415-0661 / C BGD36CFG Trouble Shooting Guide Symptom Problem Test SolutionPilot lights Wiring / Connection Right orderNot turn on Module or Valve Ing, touch black lead to ground valve bodyGas valve has An interlock deviceWhich will not allow Pilot burner to be Lit until the thermoModel BGD42CF only