Napoleon Fireplaces BGD36CFGN, BGD42CFN, BGD36CFNTR manual Model BGD42CF only

Page 48

48

BGD36CF / BGD42CF TROUBLE SHOOTING GUIDE

 

SYMPTOM

 

PROBLEM

 

TEST SOLUTION

 

 

 

 

 

 

 

 

 

Flames are consist-

 

Unit is over-fi red or under-fi red.

-

check pressure readings:

 

ently too large or too

 

 

Inlet pressure can be checked by turning screw (A) counter-clockwise 2 or 3

 

small. Carboning oc-

 

 

turns and then placing pressure gauge tubing over the test point. Gauge should

 

curs.

 

 

read 7" (minimum 4.5") water column for natural gas or 13" (11" minimum) water

 

 

 

 

column for propane. Check that main burner is operating on "HI".

 

 

 

 

Outlet pressure can be checked the same as above using screw (B). Gauge

 

 

 

 

should read 3.5" water column for natural gas or 10" water column for propane.

 

 

 

 

Check that main burner is operating on "HI".

 

 

 

 

AFTER TAKING PRESSURE READINGS, BE SURE TO TURN SCREWS CLOCK-

 

 

 

 

WISE FIRMLY TO RESEAL. DO NOT OVER TORQUE.

 

 

 

 

Leak test with a soap and water solution.

 

Flames are very ag-

Door is ajar

- tighten screws holding door in place

 

gressive.

 

 

 

 

 

 

MODEL BGD42CF ONLY:

- Restrict vent exit. See "RESTRICTING VERTICAL VENTS".

 

 

 

 

Aggressive venting action due to

- VENT HEIGHT MORE THAN 15 FEET: restrict vent exit using restrictor plate

 

 

vent height.

kit W500-0205

 

 

Main burner flame is a

Blockage in vent.

- remove blockage. In really cold conditions, ice buildup may occur on the terminal

 

blue, lazy, transparent

 

 

and should be removed as required.

 

 

fl ame.

Incorrect installation.

-

refer to Figure ## to ensure correct location of storm collars.

 

 

 

 

 

 

 

 

Carbon is being de-

Air shutter has become blocked

-

ensure air shutter opening is free of lint or other obstructions.

 

posited on glass, logs

 

 

 

 

 

Flame is impinging on the logs or

-

check that the logs are correctly positioned.

 

or combustion cham-

 

ber surfaces.

combustion chamber.

-

open air shutter to increase the primary air.

-check the input rate: check the manifold pressure and orifi ce size as specifi ed by the rating plate values.

-check that the door gasketing is not broken or missing and that the seal is tight.

-check that both 4"/5" and 7" vent liners are free of holes and well sealed at all joints.

MODEL BGD36CF(G) ONLY: - check that minimum rise per foot has been adhered to for any horizontal vent- ing.

White / grey film

Sulphur from fuel is being depos-

forms.

ited on glass, logs or combustion

 

chamber surfaces.

-clean the glass with a recommended gas fi replace glass cleaner. DO NOT CLEAN GLASS WHEN HOT.

If deposits are not cleaned off regularly, the glass may become permanently marked.

E x h a u s t smelled in headaches.

f u m e s Fireplace is spilling. room,

-ensure exhaust bracket gasket seal

-check door seal and relief fl ap seal.

-check for chimney blockage

-check that chimney is installed to building code.

-room is in negative pressure; increase fresh air supply.

-check 7"ø cap gasket on the fl ue pipe assembly.

Remote wall switch is

Wall switch is mounted upside

- reverse.

 

in "OFF" position; main

down

 

 

burner comes on when

 

 

 

 

Remote wall switch is ground-

- replace.

 

gas knob is turned to

ing.

 

 

"ON" position.

 

 

 

 

 

 

 

Remote wall switch wire is

- check for ground (short); repair ground or replace wire.

 

 

 

grounding.

 

 

 

 

 

 

 

 

 

Faulty valve.

- replace.

 

 

 

 

 

 

 

W415-0661 / C / 02.20.08

Image 48
Contents Installation Operating Instructions Table of Contents W415-0661 / C General Instructions General InformationCare of Glass and Plated Parts For example in Massachusetts StateUnit Dimensions Installation Overview38 1/2 24 1/4Venting Venting LengthsW415-0661 / C Typical Minimum and Maximum Vent Lengths See Venting SectionSpecial Vent Installations TOP Exit Installation Rear Exit InstallationPeriscope Termination Corner TerminationVenting Application Flow Chart Fireplace Vent Exit Rear Exit TOP ExitHorizontal Termination Vertical Termination When HT VT BGD36CFG TOP Exit / Horizontal TerminationDefinitions Elbow Vent Length ValuesExample Formula 2 HT + VT 24.75 feetBGD36CFG Rear Exit / Horizontal Termination Formula 1 HT VT Formula 2 HT + VT 40 feetFormula 1 HT 3.5VT Formula 2 HT + VT 24.75 feet Example Formula 2 HT + VT 40 feet Example =5 ft Formula 1 HT 3VT Formula 2 HT + VT 40 feet ExampleBGD36CFG TOP or Rear Exit Vertical Termination BGD42CF Horizontal Termination BGD42CF Vertical Termination = .03 45 + 90 + 90 +90 135 = 5.4 ft= HR + HO = 5.5 + 5.4 = 10.9 ft HT + VTFormula 1 HT 3VT Formula 2 HT + VT 40 feet Example BGD36CFG PRE-INSTALLATION Preparation Installation Wall and Ceiling ProtectionVertical Installation BGD42CF only Adjustable Firestop InstallationSpace around the pipe. Nail Headers between the joist forUsing Flexible Vent Components Horizontal AIR Terminal InstallationUsing Rigid Vent Components Vertical Venting InstallationExtended Horizontal and Corner AIR Terminal Installation GAS Installation Mobile Home InstallationOptional Wall Switch Installation Excluding BGD36CFG Restricting Vertical VentsInstalling Standoffs FramingCavity BGD36CFG BGD42CF 46 1/2BGD36CFG Minimum Mantel and Enclosure Clearances Clean Face Surround Minimum Enclosure Clearances Finished Floor InstallationConvex Concave Hearth Installation Optional Clean Face Trim KIT Installation37 3 BGD42CF Minimum Mantel and Enclosure Clearances LOG Placement Door Installation / RemovalGLASS/DOOR Replacement Finishing BGD36CF FinishingDoor Trim LOG Placement Grate InstallationGrate BGD36CFG Finishing Optional Blower Installation BGD42CF Accessing the BlowerInstalling the Blower BGD36CFG Accessing the Blower FigureGD36 Thermostatic Sensor Control Electrical Code in the United StatesBGD36CFG Burner Switch / Wiring Diagram Gauge FeetBGD36CFG Light Switch / Wiring Diagram Receptacle Wiring Diagram Operation BGD36CF & BGD42CF Lighting InstructionsTo Turn OFF GAS Maintenance For Your Safety Read Before OperatingOperation BGD36CFG Operating InstructionsAdjustments Venturi AdjustmentBGD36CFG Venturi Adjustment Pilot Burner Adjustment Excluding BGD36CFGFlame Adjustment BGD36CF Flame CharacteristicsBGD42CF Flame Characteristics BGD36CFG Flame CharacteristicsCommon Replacements BGD36CFG ReplacementsBGD42CF Replacements W415-0661 / C BGD36CFG Trouble Shooting Guide Symptom Problem Test SolutionPilot lights Wiring / Connection Right orderNot turn on Module or Valve Ing, touch black lead to ground valve bodyGas valve has An interlock deviceWhich will not allow Pilot burner to be Lit until the thermoModel BGD42CF only