Napoleon Fireplaces BGD42CFN, BGD36CFGN, BGD36CFNTR manual BGD42CF Horizontal Termination

Page 16

16

BGD42CF HORIZONTAL TERMINATION

when (HT) < (VT)

90°

Simple venting confi guration (only

 

 

one 45º and 90° elbow)

 

 

FIGURE 34

45°

REQUIRED

VERTICAL RISE IN FEET (VT)

CALCULATED HORIZONTAL VENT RUN

PLUS OFFSETS IN FEET (HT)

The shaded area within the lines represents acceptable values for HT and VT .

when (HT) > (VT) Simple venting con-

guration (only one 45º and 90° elbow)

FIGURE 36

See graph to deter- mine the required vertical rise VT for the required horizontal run HT.

REQUIRED VER-

TICAL RISE IN

INCHES VT

The shaded area within the lines represents acceptable values for HT and VT .

HORIZONTAL VENT RUN PLUS OFFSETS IN FEET (HT)

For vent confi gurations requiring more than one 45º and 90° elbow, the following formulas apply:

Formula 1: HT < VT

Formula 2: HT + VT < 40 feet

Example 1:

90°

H2

 

V1

 

FIGURE 35

 

45°

 

H1

 

V1 = 8 ft

 

VT V1= 8 ft

 

H1 = 2.5 ft

 

H2 = 2 ft

 

HR = H1 + H2 = 2.5 + 2 = 4.5 ft

 

HO = .03 (one 45° elbows + two 90° elbows - 135°)

 

= .03(225 - 135°) = 2.7 ft

 

HT = HR + HO = 4.5 + 2.7 = 7.2 ft

 

HT + VT = 7.2 + 8 = 15.2 ft

 

Formula 1: HT < VT

 

7.2< 8

Formula 2: HT + VT < 40 feet 15.2 < 40

Since both formulas are met, this vent confi guration is acceptable.

For vent confi gurations requiring more than one 45º and one 90° elbow the following formulas apply:

Formula 1: HT < 4.2 VT

 

 

 

 

Formula 2: HT + VT < 24.75 feet

90°

 

Example 2:

H1

H4

90°

90° H3

V2

V1 90° H2

45°

FIGURE 37

V1 = 4 ft

V2 = 1.5 ft

VT = V1 + V2 = 4 + 1.5 = 5.5 ft

H1 = 2 ft

H2 = 1 ft

H3 = 1 ft

H4 = 1.5 ft

HR = H1 + H2 + H3 + H4 = 2 + 1 + 1 + 1.5 = 5.5 ft

HO = .03 (one 45° elbow + four 90° elbows - 135°)

= .03(405 - 135) = 8.1 ft

 

HT = HR + HO = 5.5

+ 8.1

= 13.6 ft

HT + VT

= 13.6 +

5.5 =

19.1 ft

Formula 1:

HT < 4.2VT

4.2VT = 4.2 x 5.5 = 23.1 ft 13.6 < 16.8

Formula 2: HT + VT < 24.75 feet

19.1 < 24.75

Since both formulas are met, this vent confi guration is accept- able.

W415-0661 / C / 02.20.08

Image 16
Contents Installation Operating Instructions Table of Contents W415-0661 / C General Instructions General InformationCare of Glass and Plated Parts For example in Massachusetts StateUnit Dimensions Installation Overview38 1/2 24 1/4Venting Venting LengthsW415-0661 / C Typical Minimum and Maximum Vent Lengths See Venting SectionSpecial Vent Installations TOP Exit Installation Rear Exit InstallationPeriscope Termination Corner TerminationFireplace Vent Exit Rear Exit TOP Exit Venting Application Flow ChartHorizontal Termination Vertical Termination When HT VT BGD36CFG TOP Exit / Horizontal TerminationDefinitions Elbow Vent Length ValuesExample Formula 2 HT + VT 24.75 feetFormula 1 HT VT Formula 2 HT + VT 40 feet BGD36CFG Rear Exit / Horizontal TerminationFormula 1 HT 3.5VT Formula 2 HT + VT 24.75 feet Example Formula 2 HT + VT 40 feet Example =5 ft Formula 1 HT 3VT Formula 2 HT + VT 40 feet ExampleBGD36CFG TOP or Rear Exit Vertical Termination BGD42CF Horizontal Termination BGD42CF Vertical Termination = .03 45 + 90 + 90 +90 135 = 5.4 ft= HR + HO = 5.5 + 5.4 = 10.9 ft HT + VTFormula 1 HT 3VT Formula 2 HT + VT 40 feet Example BGD36CFG PRE-INSTALLATION Preparation Installation Wall and Ceiling ProtectionVertical Installation BGD42CF only Adjustable Firestop InstallationSpace around the pipe. Nail Headers between the joist forUsing Flexible Vent Components Horizontal AIR Terminal InstallationVertical Venting Installation Using Rigid Vent ComponentsExtended Horizontal and Corner AIR Terminal Installation GAS Installation Mobile Home InstallationOptional Wall Switch Installation Excluding BGD36CFG Restricting Vertical VentsFraming Installing StandoffsCavity BGD36CFG BGD42CF 46 1/2BGD36CFG Minimum Mantel and Enclosure Clearances Finished Floor Installation Clean Face Surround Minimum Enclosure ClearancesConvex Concave Optional Clean Face Trim KIT Installation Hearth Installation37 3 BGD42CF Minimum Mantel and Enclosure Clearances LOG Placement Door Installation / RemovalGLASS/DOOR Replacement Finishing BGD36CF FinishingGrate Installation Door Trim LOG PlacementGrate BGD36CFG Finishing Optional Blower Installation BGD42CF Accessing the BlowerInstalling the Blower BGD36CFG Accessing the Blower FigureGD36 Thermostatic Sensor Control Electrical Code in the United StatesBGD36CFG Burner Switch / Wiring Diagram Gauge FeetBGD36CFG Light Switch / Wiring Diagram Receptacle Wiring Diagram Lighting Instructions Operation BGD36CF & BGD42CFTo Turn OFF GAS Maintenance For Your Safety Read Before OperatingOperation BGD36CFG Operating InstructionsAdjustments Venturi AdjustmentBGD36CFG Venturi Adjustment Pilot Burner Adjustment Excluding BGD36CFGFlame Adjustment BGD36CF Flame CharacteristicsBGD42CF Flame Characteristics BGD36CFG Flame CharacteristicsCommon Replacements BGD36CFG ReplacementsBGD42CF Replacements W415-0661 / C BGD36CFG Trouble Shooting Guide Symptom Problem Test SolutionPilot lights Wiring / Connection Right orderNot turn on Module or Valve Ing, touch black lead to ground valve bodyGas valve has An interlock deviceWhich will not allow Pilot burner to be Lit until the thermoModel BGD42CF only