Napoleon Fireplaces BGD36CFNTR, BGD36CFGN, BGD42CFN Restricting Vertical Vents, GAS Installation

Page 23

RESTRICTING VERTICAL VENTS

BGD42CF ONLY: Vertical terminations may display a very active

ame. As this appearance is not desirable, the vent exit must be restricted using restrictor plate, W500-0205. This reduces the velocity of the exhaust gases, slowing down the fl ame pattern and creating a more traditional appearance. The plate has a series of holes to allow for adjustment.

Remove the two screws on either side of the exhaust collar inside the firebox. Install the plate as shown. Install the plate on the desired set of holes then replace the screws.

FIGURE 64

TOP OF THE

FIREBOX

FLUE COLLAR

RESTRICTOR PLATE

GAS INSTALLATION

Proceed once the vent installation is complete.

NOTE: All gas connections must be contained within the fire- place when complete.

1.Move the fi replace into position and secure to the fl oor through the 1/4" holes located at either side of the base.

2.The fi replace is designed to accept 3/8" gas supply line. The

replace is equipped with a 3/8" manual shut-off valve.

3.Connect the gas supply in accordance to local codes. In the absence thereof, install according to the National Installation Code.

4.When fl exing any gas line, support the gas valve so that the lines are not bent or kinked.

5.Check for gas leaks by brushing on a soap and water solu-

tion.

DO NOT USE OPEN FLAME.

Purge all gas lines with the glass door of the stove removed. Assure that a continuous gas flow is at the burner before re- installing the door.

OPTIONAL WALL SWITCH

INSTALLATION EXCLUDING BGD36CFG

For remote wall switch and decorative light installations for the BGD- 36CFG see section "BGD36CFG SWITCH/WIRING DIAGRAM".

For ease of accessibility, an optional remote wall switch may be installed in a convenient location. A 20ft length of millivolt wire is connected to the gas valve for the wall swtich. However, if a greater length is required route 2-strand (solid core) millivolt wire through the electrical hole located at the bottom left side of the unit. The recom- mended maximum lead length depends on wire size:

WIRE SIZE

MAX. LENGTH

14 gauge

100 feet

16 gauge

60 feet

18 gauge

40 feet

Do not connect either the wall switch, thermostat or gas valve directly to 110 volt electricity.

23

Attach the two leads to terminals 1 and 3 located on the gas valve.

FIGURE 65

MOBILE HOME INSTALLATION

This appliance may be installed as an OEM (Original Equipment Manufacturer) Installation in a manufactured home or mobile home and must be installed in accordance with the manufacturer's instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the United States or the Mobile Home Standard, CAN/CSA Z240 MH Series, in Canada. This ap- pliance is only for use with the type(s) of gas indicated on the rating plate. A conversion kit is supplied with the mobile home appliance.

This Mobile/Manufactured Home listed appliance comes factory equipped with means to secure the unit.

The fi replace is equipped with two 1/4" diameter holes located in the front left and right corners of the base. For mobile home installations, the fi replace must be fastened in place. Use #10 screws, inserted through the holes in the base to secure.

Always turn off the pilot and the fuel supply at the source, prior to moving the mobile home.

After moving the mobile home and prior to lighting the fi replace, permanently ensure that the logs are positioned correctly.

This appliance may be installed in an aftermarket permanently located, manufactured (mobile) home, where not prohibited by local codes.

This appliance is only to be used with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gasses, unless a certified kit is used.

CONVERSION KITS

The mobile home appliance is fi eld convertible between Natural Gas (NG) and Propane (LP).

To convert from one gas to another consult your Napoleon® dealer/ distributor.

W415-0661 / C / 02.20.08

Image 23
Contents Installation Operating Instructions Table of Contents W415-0661 / C For example in Massachusetts State General InstructionsGeneral Information Care of Glass and Plated Parts24 1/4 Unit DimensionsInstallation Overview 38 1/2Venting Lengths VentingW415-0661 / C See Venting Section Typical Minimum and Maximum Vent LengthsCorner Termination Special Vent InstallationsTOP Exit Installation Rear Exit Installation Periscope TerminationHorizontal Termination Vertical Termination Venting Application Flow ChartFireplace Vent Exit Rear Exit TOP Exit Elbow Vent Length Values When HT VTBGD36CFG TOP Exit / Horizontal Termination DefinitionsFormula 2 HT + VT 24.75 feet ExampleFormula 1 HT 3.5VT Formula 2 HT + VT 24.75 feet Example BGD36CFG Rear Exit / Horizontal TerminationFormula 1 HT VT Formula 2 HT + VT 40 feet Formula 1 HT 3VT Formula 2 HT + VT 40 feet Example Formula 2 HT + VT 40 feet Example =5 ftBGD36CFG TOP or Rear Exit Vertical Termination BGD42CF Horizontal Termination HT + VT BGD42CF Vertical Termination= .03 45 + 90 + 90 +90 135 = 5.4 ft = HR + HO = 5.5 + 5.4 = 10.9 ftFormula 1 HT 3VT Formula 2 HT + VT 40 feet Example Installation Wall and Ceiling Protection BGD36CFG PRE-INSTALLATION PreparationHeaders between the joist for Vertical InstallationBGD42CF only Adjustable Firestop Installation Space around the pipe. NailHorizontal AIR Terminal Installation Using Flexible Vent ComponentsExtended Horizontal and Corner AIR Terminal Installation Using Rigid Vent ComponentsVertical Venting Installation Restricting Vertical Vents GAS InstallationMobile Home Installation Optional Wall Switch Installation Excluding BGD36CFGCavity Installing StandoffsFraming 46 1/2 BGD36CFG BGD42CFBGD36CFG Minimum Mantel and Enclosure Clearances Convex Concave Clean Face Surround Minimum Enclosure ClearancesFinished Floor Installation 37 3 Hearth InstallationOptional Clean Face Trim KIT Installation BGD42CF Minimum Mantel and Enclosure Clearances Finishing BGD36CF Finishing LOG PlacementDoor Installation / Removal GLASS/DOOR ReplacementGrate Door Trim LOG PlacementGrate Installation BGD36CFG Finishing BGD36CFG Accessing the Blower Figure Optional Blower InstallationBGD42CF Accessing the Blower Installing the BlowerElectrical Code in the United States GD36 Thermostatic Sensor ControlGauge Feet BGD36CFG Burner Switch / Wiring DiagramBGD36CFG Light Switch / Wiring Diagram Receptacle Wiring Diagram To Turn OFF GAS Operation BGD36CF & BGD42CFLighting Instructions Operating Instructions MaintenanceFor Your Safety Read Before Operating Operation BGD36CFGPilot Burner Adjustment Excluding BGD36CFG AdjustmentsVenturi Adjustment BGD36CFG Venturi AdjustmentBGD36CFG Flame Characteristics Flame AdjustmentBGD36CF Flame Characteristics BGD42CF Flame CharacteristicsBGD36CFG Replacements Common ReplacementsBGD42CF Replacements W415-0661 / C Symptom Problem Test Solution BGD36CFG Trouble Shooting GuideIng, touch black lead to ground valve body Pilot lights Wiring / ConnectionRight order Not turn on Module or ValveLit until the thermo Gas valve hasAn interlock device Which will not allow Pilot burner to beModel BGD42CF only