Napoleon Fireplaces BGD36CFGN, BGD42CFN, BGD36CFNTR manual Framing, Installing Standoffs, Cavity

Page 24

24

FRAMING

BGD36CF(G)

MINIMUM CLEARANCE TO COMBUSTIBLE CONSTRUCTION FROM FIREPLACE AND VENT SURFACES:

It is not necessary to install a hearth extension with this fireplace sys- tem. Objects placed in front of the fireplace should be kept a minimum of 48" away from the front face.

Non-Combustible framing: Top

Combustible framing:

Sides, back, and bottom of the unit Top

Non-combustible fi nishing: Top

0" to stand-offs if using optional clean face surround

0" to stand-offs

3 1/2" to stand-offs if using optional clean face surround

6 1/2" if using optional clean face surround

When roughing in the fi replace, raise the fireplace to accommodate for the thickness of the fi nished fl oor materials, i.e. tile, carpeting, hard wood, which if not planned for will interfere with the opening of the lower access door and the installation of many decorative flashing accessories.

Note: In order to avoid the possibility of exposed insulation or vapor barrier coming in contact with the fi replace body, it is recommended that the walls of the fi replace enclosure be “fi nished” (ie: drywall/ sheetrock), as you would fi nish any other outside wall of a home. This will ensure that clearance to combustibles is maintained within

Combustible fi replace fi nishing:

 

Sides, bottom and top

0" to fi replace edge

Enclosure top

8 1/4" to top of fi replace

Recessed depth

17 1/4"

Sides and bottom of the vent pipe

1"

Top of vent pipe

2"

Ceiling

72" from bottom of unit

HORIZONTAL VENT SECTIONS: - A minimum clearance of 1" at the bottom and sides of the vent and 2" at the top on all horizontal runs to combustibles is required. Use fi restop spacer W010-1774 (supplied).

VERTICAL VENT SECTIONS: - A minimum of 1" all around the vent pipe on all vertical runs to combustibles is required except for clearances in

replace enclosures*. See "MINIMUM ENCLOSURE CLEARANCES" section. Use fi restop spacer W500-0096 (not supplied).

* Vertical vent sections in fi replace enclosures require a minimum of 1 1/2" all around the vent pipe.

BGD42CF

MINIMUM CLEARANCE TO COMBUSTIBLE CONSTRUCTION FROM

FIREPLACE AND VENT SURFACES:

 

Combustible framing:

 

Top, sides, back and bottom of the unit

0" to stand-offs

Non-combustible fi nishing:

 

Top

6 1/2" to fi replace edge

Combustible fi replace fi nishing:

 

Sides and bottom

0" to fi replace edge

Enclosure top

13 1/2" to top of fi replace

Recessed depth

25"

Top, sides and bottom of vent pipe

2"

Ceiling

72" from bottom of unit

HORIZONTAL VENT SECTIONS: A minimum clearance of 2" all around the vent pipe on all horizontal runs to combustibles is required. Use firestop spacer W010-1778 (supplied).

VERTICAL VENT SECTIONS: A minimum of 1" all around the vent pipe on all vertical runs to combustibles is required. Use firestop spacer W500- 0028 (not supplied).

INSTALLING STANDOFFS

Both the BGD36CF(G) and BGD42CF are supplied with two standoffs. For convenience, the standoffs have been shipped fl at and located on the top at the front. Before framing ensure the standoffs are bent up and screwed into place ensuring a height of 4.5".

BGD36 ILLUSTRATION

FIGURE 66

NOTE: The information and dimensions in this section represent the minimum clearances to combustible material.

It is best to frame your fireplace after it is positioned and the vent sys- tem is installed. Use 2x4's and frame to local building codes.

BGD36CF(G) ONLY: A steel header is required if using optional clean face surround.

the cavity.

Combustible materials may be installed fl ush with the front of the fire- place but must not cover any of the black face-areas of the fireplace. Non-combustible material (brick, stone or ceramic tile) may protrude in these areas but must not restrict glass door removal.

BGD36CF(G)

FIGURE 67

BGD42CF

FIGURE 68

W415-0661 / C / 02.20.08

Image 24
Contents Installation Operating Instructions Table of Contents W415-0661 / C General Instructions General InformationCare of Glass and Plated Parts For example in Massachusetts StateUnit Dimensions Installation Overview38 1/2 24 1/4Venting Venting LengthsW415-0661 / C Typical Minimum and Maximum Vent Lengths See Venting SectionSpecial Vent Installations TOP Exit Installation Rear Exit InstallationPeriscope Termination Corner TerminationVenting Application Flow Chart Fireplace Vent Exit Rear Exit TOP ExitHorizontal Termination Vertical Termination When HT VT BGD36CFG TOP Exit / Horizontal TerminationDefinitions Elbow Vent Length ValuesExample Formula 2 HT + VT 24.75 feetBGD36CFG Rear Exit / Horizontal Termination Formula 1 HT VT Formula 2 HT + VT 40 feetFormula 1 HT 3.5VT Formula 2 HT + VT 24.75 feet Example Formula 2 HT + VT 40 feet Example =5 ft Formula 1 HT 3VT Formula 2 HT + VT 40 feet ExampleBGD36CFG TOP or Rear Exit Vertical Termination BGD42CF Horizontal Termination BGD42CF Vertical Termination = .03 45 + 90 + 90 +90 135 = 5.4 ft= HR + HO = 5.5 + 5.4 = 10.9 ft HT + VTFormula 1 HT 3VT Formula 2 HT + VT 40 feet Example BGD36CFG PRE-INSTALLATION Preparation Installation Wall and Ceiling ProtectionVertical Installation BGD42CF only Adjustable Firestop InstallationSpace around the pipe. Nail Headers between the joist forUsing Flexible Vent Components Horizontal AIR Terminal InstallationUsing Rigid Vent Components Vertical Venting InstallationExtended Horizontal and Corner AIR Terminal Installation GAS Installation Mobile Home InstallationOptional Wall Switch Installation Excluding BGD36CFG Restricting Vertical VentsInstalling Standoffs FramingCavity BGD36CFG BGD42CF 46 1/2BGD36CFG Minimum Mantel and Enclosure Clearances Clean Face Surround Minimum Enclosure Clearances Finished Floor InstallationConvex Concave Hearth Installation Optional Clean Face Trim KIT Installation37 3 BGD42CF Minimum Mantel and Enclosure Clearances LOG Placement Door Installation / RemovalGLASS/DOOR Replacement Finishing BGD36CF FinishingDoor Trim LOG Placement Grate InstallationGrate BGD36CFG Finishing Optional Blower Installation BGD42CF Accessing the BlowerInstalling the Blower BGD36CFG Accessing the Blower FigureGD36 Thermostatic Sensor Control Electrical Code in the United StatesBGD36CFG Burner Switch / Wiring Diagram Gauge FeetBGD36CFG Light Switch / Wiring Diagram Receptacle Wiring Diagram Operation BGD36CF & BGD42CF Lighting InstructionsTo Turn OFF GAS Maintenance For Your Safety Read Before OperatingOperation BGD36CFG Operating InstructionsAdjustments Venturi AdjustmentBGD36CFG Venturi Adjustment Pilot Burner Adjustment Excluding BGD36CFGFlame Adjustment BGD36CF Flame CharacteristicsBGD42CF Flame Characteristics BGD36CFG Flame CharacteristicsCommon Replacements BGD36CFG ReplacementsBGD42CF Replacements W415-0661 / C BGD36CFG Trouble Shooting Guide Symptom Problem Test SolutionPilot lights Wiring / Connection Right orderNot turn on Module or Valve Ing, touch black lead to ground valve bodyGas valve has An interlock deviceWhich will not allow Pilot burner to be Lit until the thermoModel BGD42CF only