Heat & Glo LifeStyle SL-750TRS-IPI-D owner manual MAX. = 16 FT 4.8m + V 1 + H MAX. = 40 FT 12.2m

Page 27

VENTING WITH TWO (2) 90o ELBOWS

NATURAL GAS

 

MODEL: SL-350TRS-C

MODELS: SL-550TRS-D, SL-750TRS-D

V (MIN.)

H (MAX.)

H (MAX.)

 

90o Elbow on Top

2.5 FT (762mm)

2 FT (610mm)

1 FT (305mm)

3 FT (914mm)

3 FT (914mm)

2 FT (610mm)

4 FT (1.22m)

4 FT (1.22m)

3 FT (914mm)

6 FT (1.86m)

6 FT (1.86m)

4 FT (1.22m)

8 FT (2.48m)

8 FT (2.48m)

5 FT (1.52m)

16 FT (4.8m)

16 FT (4.8m)

H MAX. = 16 FT (4.8m)

V + V1 + H MAX. = 40 FT (12.2m)

 

 

 

 

VENTING WITH TWO (2) 90o ELBOWS

PROPANE

MODELS: SL-350TRS-C, SL-550TRS-D, SL-750TRS-D

V (MIN.)

 

H (MAX.)

 

90o Elbow on Top

NOTALLOWED

1 FT (305mm)

 

2 FT (610mm)

 

2 FT (610mm)

 

4 FT (1.22m)

 

3 FT (914mm)

 

6 FT (1.86m)

 

4 FT (1.22m)

 

8 FT (2.48m)

 

5 FT (1.52m)

 

16 FT (4.8m)

 

H MAX. = 16 FT (4.8m)

V + V1 + H MAX. = 40 FT (12.2m)

 

 

 

 

H

V1

V

NOTE: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installa- tion (see Figure 9).

Use SL D-Series components only.

Figure 16. Venting with Two 90° Elbows

Heat & Glo • SL-350TRS-C, SL-550/750TRS-IPI-D2065-985 Rev. J • 5/06

27

Image 27
Contents SL-750TRS-IPI-D SL-550TRS-IPI-D SL-350TRS-C Installation and OperationSafety and Warning Information Table of Contents SL-350TRS-C Log Set AssemblySL-350TRS-C NG, LP Service Parts ListStanding Pilot Ignition Valve AssemblySL-550TRS-IPI-D SL-550TRS-IPI-D Part number list on following Log Set AssemblySL-750TRS-IPI-D Intermittent Pilot Ignition Valve Assembly Service Parts SL-750TRS-IPI-D, SL-550TRS-IPI-DCertification High Altitude InstallationsInstallation Codes Appliance CertificationRequirements for the Commonwealth of Massachusetts Vent Directly BELOW. Keep Clear of ALL OB- StructionsManufacturer Requirements Pre-install Preparation Introducing the Heat & Glo Gas AppliancesANY Such Action MAY Possibly Cause a Fire Hazard Diagram of the SL-750TRS-IPI-D GAS Line Electrical Access Diagram of the SL-350TRS-C AccessConstructing the Appliance Chase Locating the ApplianceClearance Requirements Framing the Appliance Framing Dimensions34.93mm AT Each Joint 47 3/4 SL D-SERIES Components in ANY Vent Installing the Vent SystemSystem Configuration Identifying Vent ComponentsFlex Vent Straight UP Vertical VentingWith TWO 900 Elbows Venting with One 90 Elbow Use SL D-Series components only Use DVP-Series Components onlyVenting with Two 90 Elbows Venting with TWO 2 90 o Elbows MAX. = 16 FT 4.8m + V 1 + H MAX. = 40 FT 12.2m Venting with Three 90 elbows Venting with Three 3 90 o Elbows + H 1 MAX. = 16 FT 4.8m + V 1 + H + H MAX. = 40 FT 12.2m Venting with Four 90 elbows DVP Series Venting Only Go to Install FirestopsAttach the First Vent Component to the Starting Collars SL-D and SL-Flex Series Venting OnlyHole and Vent Pipe DVP, SL-D and SL-Flex Series VentingFor All Venting Vent TerminationSL-Series Venting Only For DVP Venting OnlyVent Termination Minimum Clearances Alcove ApplicationsMinimum Height from Roof to Lowest Discharge Opening Millivolt System Positioning, Leveling, and Securing the ApplianceGas Control Systems Standing Pilot Ignition SystemGas Supply Line Gas Pressure RequirementsPressure Natural Gas Propane Wall Switch Wiring the ApplianceFor Standing Pilot Ignition Wiring Appliance Requirements Optional AccessoriesIntermittent Pilot Ignition IPI Wiring Diagram Operation using Battery PowerNER FinishingPositioning the Logs Installing the TrimShutter Settings Glass SpecificationsLighting the Appliance After the InstallationDouble-check for faulty components Before Lighting the ApplianceImportant Turn OFF the GAS Before Servicing Your Appliance Appliance Maintenance