Heat & Glo LifeStyle SL-750TRS-IPI-D owner manual Gas Supply Line, Gas Pressure Requirements

Page 39

Step 6. The Gas Supply Line

NOTE: Have the gas supply line installed in accordance with local building codes by a qualified installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter).

NOTE: Before the first firing of the appliance, the gas supply line should be purged of any trapped air.

NOTE: Consult local building codes to properly size the gas supply line leading to the 1/2 inch (13mm) hook-up at the unit.

This gas appliance is designed to accept a 1/2 inch (13mm) gas supply line. To install the gas supply line:

GAS ACCESS

Figure 34. Gas Supply Line

USE A WRENCH ON SHUT-OFF VALVE WHEN TIGHTENING GAS LINE

MANUAL

SHUT-OFF VALVE

GAS VALVE

FLEX

CONNECTOR

A listed (and Commonwealth of Massachusetts approved) 1/2 inch (13mm) tee-handle manual shut-off valve and a listed flexible gas connector are connected to the 1/2 inch (13mm) inlet of the control valve. NOTE: If substi- tuting for these components, please consult local codes for compliance.

Locate the gas line access hole in the outer casing of the appliance.

The gas line may be run from either side of the appli- ance provided the hole in the outer wrap does not exceed 2” in diameter and it does not penetrate the actual firebox.

Open the appliance lower grille, insert the gas supply line through the gas line hole, and connect it to the shut-off valve.

When attaching the pipe, support the control so that the lines are not bent or torn.

After the gas line installation is complete, all connec- tions must be tightened and checked for leaks with a commercially-available, non-corrosive leak check solu- tion. Be sure to rinse off all leak check solution following testing.

!WARNING: DO NOT USE AN OPEN FLAME TO CHECK FOR GAS LEAKS.

Insert insulation from the outside of the appliance and pack the insulation tightly to totally seal between the pipe and the outer casing.

At the gas line access hole the gap between the supply piping and gas access hole can be plugged with non- combustible insulation to prevent cold air infiltration.

Step 7. Gas Pressure Requirements

Pressure requirements for Heat & Glo gas appliances are shown in the table below.

Pressure

Natural Gas

Propane

Minimum

5.0 inches

11.0 inches

Inlet Pressure

w.c.

w.c.

Maximum Inlet

14.0 inches

14.0 inches

Gas Pressure

w.c.

w.c.

Manifold

3.5 inches

10.0 inches

Pressure

w.c.

w.c.

 

 

 

A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is provided on the inlet and outlet side of the gas control for a test gauge connection to measure the manifold pressure. Use a small flat blade screwdriver to crack open the screw in the center of the tap. Position a rubber hose over the tap to obtain the pressure reading.

The appliance and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of one-half (1/2) psig (3.5 kPa).

The appliance must be isolated from the gas supply piping system by closing its individual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than one-half (1/2) psig (3.5 kPa).

Heat & Glo • SL-350TRS-C, SL-550/750TRS-IPI-D2065-985 Rev. J • 5/06

39

Image 39
Contents SL-750TRS-IPI-D SL-550TRS-IPI-D SL-350TRS-C Installation and OperationSafety and Warning Information Table of Contents SL-350TRS-C Log Set AssemblySL-350TRS-C NG, LP Service Parts ListStanding Pilot Ignition Valve AssemblySL-550TRS-IPI-D SL-550TRS-IPI-D Part number list on following Log Set AssemblySL-750TRS-IPI-D Intermittent Pilot Ignition Valve Assembly Service Parts SL-750TRS-IPI-D, SL-550TRS-IPI-DCertification High Altitude InstallationsInstallation Codes Appliance CertificationRequirements for the Commonwealth of Massachusetts Vent Directly BELOW. Keep Clear of ALL OB- StructionsManufacturer Requirements Pre-install Preparation Introducing the Heat & Glo Gas AppliancesANY Such Action MAY Possibly Cause a Fire Hazard Diagram of the SL-750TRS-IPI-D GAS Line Electrical Access Diagram of the SL-350TRS-C AccessConstructing the Appliance Chase Locating the ApplianceClearance Requirements Framing the Appliance Framing Dimensions34.93mm AT Each Joint 47 3/4 SL D-SERIES Components in ANY Vent Installing the Vent SystemSystem Configuration Identifying Vent ComponentsFlex Vent Straight UP Vertical VentingWith TWO 900 Elbows Venting with One 90 Elbow Use SL D-Series components only Use DVP-Series Components onlyVenting with Two 90 Elbows Venting with TWO 2 90 o Elbows MAX. = 16 FT 4.8m + V 1 + H MAX. = 40 FT 12.2m Venting with Three 90 elbows Venting with Three 3 90 o Elbows + H 1 MAX. = 16 FT 4.8m + V 1 + H + H MAX. = 40 FT 12.2m Venting with Four 90 elbows DVP Series Venting Only Go to Install FirestopsAttach the First Vent Component to the Starting Collars SL-D and SL-Flex Series Venting OnlyHole and Vent Pipe DVP, SL-D and SL-Flex Series VentingFor All Venting Vent TerminationSL-Series Venting Only For DVP Venting OnlyVent Termination Minimum Clearances Alcove ApplicationsMinimum Height from Roof to Lowest Discharge Opening Millivolt System Positioning, Leveling, and Securing the ApplianceGas Control Systems Standing Pilot Ignition SystemGas Supply Line Gas Pressure RequirementsPressure Natural Gas Propane Wall Switch Wiring the ApplianceFor Standing Pilot Ignition Wiring Appliance Requirements Optional AccessoriesIntermittent Pilot Ignition IPI Wiring Diagram Operation using Battery PowerNER FinishingPositioning the Logs Installing the TrimShutter Settings Glass SpecificationsLighting the Appliance After the InstallationDouble-check for faulty components Before Lighting the ApplianceImportant Turn OFF the GAS Before Servicing Your Appliance Appliance Maintenance