Gas-Fired Products PTS Series, PTU Series manual Single Heater Venting Vertical Through the Roof

Page 36

SINGLE HEATER VENTING (VERTICAL THROUGH THE ROOF)

1.When venting the heater to outside of building through a roof, use single-wall metal pipe. This is to be constructed of galvanized sheet metal or other approved noncombustible corrosion-resistant material as allowed by state or local codes.

2.A vent passing through a combustible roof shall extend through an approved clearance roof thimble. Double-wall, Type B vent must be used for the portion of the vent system which passes through the roof. An approved vent cap (Leslie “VersaCap”-Type B or equal) must be attached to end of the flue.

3.The maximum equivalent length of vent pipe should be carefully observed. A safety switch in the heater is designed to shut the heater off before excessive flue restriction causes bad combustion. Refer to the Vent Sizing Table for maximum vent lengths and vent pipe diameter.

4.Joints between sections of piping shall be fastened by sheet metal screws or other approved means and should be sealed to prevent leakage of flue gas into building. Aluminum or Teflon tape suitable for 550ºF (3M Company tapes 433 or 363) or silicone sealant is recommended.

5.All portions of the vent pipe shall be supported to prevent from sagging (6’ spacing is recommended).

6.When the vent pipe passes through areas where the ambient temperature is likely to induce condensation of the flue gases, the vent pipe should be insulated and a condensation drain should be provided.

7.Minimum clearance for single-wall flue pipe to combustible material shall be 6 inches. This may be reduced when the combustible material is protected as specified in the National Fuel Gas Code or the authority having jurisdiction.

8.Single-wall metal pipe shall not originate in any unoccupied attic or concealed space and shall not pass through any attic, inside wall or concealed space, or through any floor. For the installation of a single-wall metal pipe through an exterior combustible wall, refer to latest edition of the National Fuel Gas Code or the authority having jurisdiction.

9.A venting system shall terminate at least 3 ft. above any forced air inlet located within 10 ft.

Vent Cap (Leslie VersaCap Type B)

4” Vent Pipe (vertical position)

#10 Self-Drill

ScrewsFlashing (typical)

2” (5cm) Clearance Thimble

Seal Joint

4” Vent Elbow and Annular

Space

Flue Adapter

Collar

 

 

 

 

 

 

 

 

 

 

2 ft (77cm) minimum

 

 

 

 

 

 

 

 

(when no wall or

 

 

 

 

 

 

 

parapet exists)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 ft

(77cm)

 

 

10 ft (305cm)

 

 

 

minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or less

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4” Diameter

 

 

Wall or Parapet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vent

 

 

 

 

 

 

 

 

 

 

 

 

 

SINGLE HEATER VENTING (HORIZONTAL THROUGH SIDEWALL)

When venting the heater horizontally through a combustible outside sidewall, the same requirements listed previously for venting Vertical Through The Roof apply except as follows:

1.A vent passing through a combustible wall must pass through an approved clearance thimble (Air-Jet #4VT or Ameri-Vent #4EWT or other thimbles that are listed by a nationally recognized testing agency.

2.An approved vent cap (Breidert-Type L or equal) must be attached to the end of the vent pipe.

NOTE: To minimize problems associated with condensation in long horizontal runs, vent pipe can be insulated.

3.Use the following correction factors to obtain the equivalent length when elbows are used:

c.Subtract 10 ft. for each elbow beyond 15 ft. from the heater.

d.Subtract 15 ft. for each elbow within 15 ft. of the heater.

4.Limit to (2) 90º elbows in the vent system.

5.When venting through a sidewall, the horizontal vent pipe shall fall not less than 1/2 inch per 20 feet from the start of the vent system to the vent terminal. All portions of the vent pipe shall be supported to prevent sagging. (6’ spacing is recommended)

6.A minimum clearance of 6 inches must be maintained between the outside wall and vent cap.

Form #43343330

 

May 08

–35–

Image 36
Contents Installation and Operation Instructions Table of Contents Safety Installer ResponsibilityInstallation Requirements General InformationFor Canada only High AltitudeMinimum Clearances to Combustibles Minimum Clearances to CombustiblesPTS/PTU Specifications Packing ListBurner Package Numbers Natural GASPTU 40-200 Body Package Descriptions Reflector, 4’ 11 ½’ Accessories End Reflector Accessory PackageExhaust Hood Package Typical Layouts PTU / PTS Series Emitter Length Body Length ModelTypical Assembly Layout Poisonous GAS and Soot HazardPTS Series Dimensions PTU Series Heater Assembly Joining of Tube SectionsTypical Assembly Overview PTU 40FT Shown Typical Suspension Methods Suspension HazardAssembly of Tube Sections CUT HazardAssembly of Extension Section MIN 8’ MAX 10’ Between HangersInserting Turbulators Assembly Hazard Adding ReflectorsAdding Optional 90º Elbow PTS only Adding Optional Corner Reflector PTS onlyAdding 180U-Bend PTU only Adding Optional U-BEND Reflector PTU onlyAttaching Burner BOX Assembly Connecting the Tiss System InstructionsEnd View Angle Mounted Heaters only GAS Connections and Regulations Do not USE AN Open Flame of ANY Kind to Test for LeaksKEY Dimensions and Components of the GAS Connections Instructions for Pressure Test Gauge Connection Supply PressureManifold Pressure Combination GAS Valve is Factory SET Electrical Connections STEP-OPENING GAS Control ValveIgnition Module Terminal Designations 24VAC/R TH/WPS/W GNDLine Voltage 120V Thermostat Connections Single Heater Line Voltage 120V Thermostat Connections Multiple HeatersLOW Voltage 24V Thermostat Connections Single Heaters Venting Carbon Monoxide HazardSingle Heater Venting Vertical Through the Roof Single Heater Venting Horizontal Through Sidewall#10 Self-Drill Vent Pipe Screws Multiple Heater Vertical venting arrangement PTS/PTU Common Vent DiameterAIR for Combustion Direct Outside AIR for CombustionVertical Lighting and Shutdown Instructions Sequence of OperationBurner Component Locations Cleaning and Maintenance Electric Shock & Explosion HazardTroubleshooting Guide Form Form #43343330 May Replacing Parts Removal of Main Burner and ElectrodesRemoval of GAS Valve and Manifold Assembly AIR Switch Pressure CheckIgnition System Checks To Check Flame Sensor CircuitInstallation Data Ignition Module DiagnosticsReplacement Parts Guide Burner BOX FastenersLabels/Manual 22c 22b 22a 40a 17a Body Components Description