Gas-Fired Products PTU Series, PTS Series manual Direct Outside AIR for Combustion

Page 39

B. INDIRECT VENTING (UNVENTED HEATERS) — This heater requires ventilation in the building to dilute the products of combustion and provide fresh air for efficient combustion. Where unvented heaters are used, gravity or mechanical means shall be provided to supply and exhaust at least 4 CFM per 1,000 Btu/hr input of installed heaters. Exhaust vents must be located at the highest point above and in the vicinity of the heaters, and the inlet vents must be located below the level of the heaters. An exhaust hood (Part #42924000) must be placed on the flue adapter collar located on the end of the last body section when used unvented and must be mounted only in an downward position as shown.

#10 Self-Drill

Screws

 

Exhaust Hood

Flue Adapter

(mount in a downward

Collar

position)

Exhaust Hood Attachment (for UNVENTED use)

17.0) AIR FOR COMBUSTION

If indoor combustion air is to be supplied for a tightly enclosed area, one square inch of free area opening shall be provided below the heater for each 1,000 Btu/hr of heater input. Adequate clearances around the air inlet screen must be maintained at all times. In larger open areas of buildings, infiltration normally is adequate to provide air for combustion.

17.1) DIRECT OUTSIDE AIR FOR COMBUSTION

Outside combustion air should be supplied directly to the heater when the building is subject to negative pressure, or when contaminants or high humidity are present in the building air. These contaminants include paints, solvents, corrosive vapors or any other foreign particles that may cause damage to the heater or result in poor combustion.

Outside combustion air can be brought directly to the heater by a 4” diameter duct less than 50 ft. long or equivalent (see table in Section 16). This is attached to the 4” diameter starting collar (supplied with heater). The starting collar is fitted to the rear of the burner box cabinet as shown below. An approved vent cap must be placed directly on the end of the outside combustion air inlet pipe. The combustion air inlet should be not less than 3 ft. (0.9m), either vertically or horizontally, from the flue vent termination. The air intake terminal must be located not less than 1 ft. (30cm) above grade. It is good installation practice to supply combustion air from the same pressure zone as the vent outlet. Avoid bringing combustion air to the heater from an attic space. There is no guarantee that adequate combustion air will be supplied.

If the heater is installed less than 2 ft. from the ceiling, a combustion air inlet kit PN 44129510 must be provided to allow for expansion/contraction of straight tube heaters (PTS series).

In colder climates, where necessary, insulate the outside combustion air duct. In high humidity applications, the burner box should be sealed with silicone sealer.

 

Form #43343330

–38–

May 08

Image 39
Contents Installation and Operation Instructions Table of Contents General Information SafetyInstaller Responsibility Installation RequirementsHigh Altitude For Canada onlyMinimum Clearances to Combustibles Minimum Clearances to CombustiblesPTS/PTU Packing List SpecificationsNatural GAS Burner Package NumbersPTU 40-200 Body Package Descriptions Reflector, 4’ 11 ½’ End Reflector Accessory Package AccessoriesExhaust Hood Package Emitter Length Body Length Model Typical Layouts PTU / PTS SeriesPoisonous GAS and Soot Hazard Typical Assembly LayoutPTS Series Dimensions PTU Series Joining of Tube Sections Heater AssemblyTypical Assembly Overview PTU 40FT Shown Suspension Hazard Typical Suspension MethodsCUT Hazard Assembly of Tube SectionsMIN 8’ MAX 10’ Between Hangers Assembly of Extension SectionInserting Turbulators Adding Reflectors Assembly HazardAdding Optional Corner Reflector PTS only Adding Optional 90º Elbow PTS onlyAdding Optional U-BEND Reflector PTU only Adding 180U-Bend PTU onlyAttaching Burner BOX Assembly Instructions Connecting the Tiss SystemEnd View Angle Mounted Heaters only Do not USE AN Open Flame of ANY Kind to Test for Leaks GAS Connections and RegulationsKEY Dimensions and Components of the GAS Connections Instructions for Pressure Test Gauge Connection Supply PressureManifold Pressure Combination GAS Valve is Factory SET STEP-OPENING GAS Control Valve Electrical ConnectionsGND Ignition Module Terminal Designations 24VAC/RTH/W PS/WLine Voltage 120V Thermostat Connections Single Heater Line Voltage 120V Thermostat Connections Multiple HeatersLOW Voltage 24V Thermostat Connections Single Heaters Carbon Monoxide Hazard VentingSingle Heater Venting Horizontal Through Sidewall Single Heater Venting Vertical Through the Roof#10 Self-Drill Vent Pipe Screws PTS/PTU Common Vent Diameter Multiple Heater Vertical venting arrangementDirect Outside AIR for Combustion AIR for CombustionVertical Sequence of Operation Lighting and Shutdown InstructionsBurner Component Locations Electric Shock & Explosion Hazard Cleaning and MaintenanceTroubleshooting Guide Form Form #43343330 May Removal of Main Burner and Electrodes Replacing PartsAIR Switch Pressure Check Removal of GAS Valve and Manifold AssemblyTo Check Flame Sensor Circuit Ignition System ChecksIgnition Module Diagnostics Installation DataFasteners Replacement Parts Guide Burner BOXLabels/Manual 22c 22b 22a 40a 17a Description Body Components