FireplaceXtrordinair 44 DV XXL EF manual Gas Line Requirements, Fuel, Gas Line Connection

Page 12

1 2

Installation (for qualified installers only)

Gas Line Requirements

!The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI 223.1 and the requirements listed below.

!The fireplace and gas control valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 psig. For pressures under 1/2 psig, isolate the gas supply piping by closing the manual shutoff valve.

!Leak test all gas line joints and the gas control valve prior to and after starting the fireplace.

Fuel

This fireplace is designed either for natural gas or for propane (but not for both). Check the sticker on the top of the gas control valve to make sure the correct fuel is used.

Gas Line Connection

A manual shutoff valve is required for installation (within 3’ of the heater or inside the fireplace). T-Handle gas cocks are required in Massachusetts in compliance with code 248CMR.

The 1" diameter access hole is located 2-3/8" above the base of the fireplace. Cut an "X" in the gasket covering the inlet and insert the gas line through the gasket.

A shutoff valve may be placed within the fireplace

The modulating remote shield may be removed to ease installation. 18-1/2"

If the gas line is routed from the

6-1/2"

6-3/4"

right side, bend the flex tube 180°.

3/8" M.P.T to 1/2" O.D. Fitting (Factory installed)

Gas Control Valve

-- OR --

 

 

-- OR --

 

 

The included

 

 

fitting accepts a

10" Flex Tube

3/8" M.P.T. or

(shipped with the fireplace - min. bending radius is 3/4")

1/2" F.P.T.

 

 

Gas Inlet Pressure:

 

Standard Input Pressure

 

 

Natural Gas

7" W.C. (1.74 kPA)

Propane

 

13" W.C. (2.73 kPA)

If the pressure is not sufficient, make sure the piping used is large enough, the supply regulator is adequately adjusted, and the total gas load for the residence does not exceed the amount supplied.

The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank) should supply gas at the suggested input pressure listed above. Contact the local gas supplier if the regulator is at an improper pressure.

Travis Industries

4050114

1 0 0 - 0 1 1 4 9

Image 12
Contents DV XXL EF Manual Introduction IntroductionImportant Information Travis Industries 4050114 0 0 1 1 4Safety Precautions If YOU Smell GAS 4050114 0 0 1 1 4 Travis IndustriesThis Manual Features and Specifications Features Installation OptionsHeating Specifications Natural Gas Propane Installation Warnings Packing ListAdditional Items Required Installation Overview Recommended Installation ProcedureFireplace Placement Requirements Minimum Framing DimensionsClearances Vertical StandoffCorner Installations Raised FireplacesGas Line Requirements FuelGas Line Connection Gas Inlet PressureElectrical Connection Fireplace junction boxVent Requirements Altitude ConsiderationsPart Numbers for 8 Diameter Vent Horizontal RunsVent Installation Vertical Vent RequirementsApproved Vent Configurations Restrictor PositionElbows Measuring Vent LengthsVertical Terminations with 0, 2, or 4 45 Offsets Zero or Two 45 Offsets Four 45 OffsetsHorizontal Terminations with One Vertical Elbow Horizontal Terminations with Three Vertical Elbows Vertical Terminations with Two Vertical 90 Elbows Termination Requirements see the illustration below Hearth Requirements Floor Mounted FireplacesFacing Requirements Minimum Top Facing ClearanceFace Dimensions Modifying the Face Angle for Rectangular FacesFireplace Facing Detail Facing Example Facing Under 1 Thick FireplaceFacing Example Facing Over 1 Thick Arched FacesMantel Requirements Combustible or Non-Combustible MantelsMinimum Mantel Clearance Re-Attaching the Glass Frame Arch Covers both sidesGlass Frame Removal and Installation Place the Rear Log Place the Middle Logs Placing the Front Log Placing the Twigs Correct Arch Faces Architectural Faces Operation3 Before You Begin Location of Controls See explanation below8Operation Starting The Pilot FlameAdjusting the Flame Height Starting the Fireplace for the First TimeTurning the Fireplace On and Off Adjusting the Blower Speed Optional Power Heat Duct0Operation Normal Operating SoundsYearly Service Procedure Maintaining Your Fireplaces AppearanceMaintenance Troubleshooting TableHow this Fireplace Works What Turns the Main Burners On and OffWhat Prevents Gas Buildup Wiring Diagram Replacement Parts ListSafety Label Fireplace Xtrordinair 44DVXXL6Limited 7 Year Warranty Years 1 & 2 Coverage Parts & LaborYears 3 Through 5 Coverage Parts & Labor Years 6 & 7 Coverage Parts onlyBurner Replacement LP Conversion InstructionsOptional Equipment for qualified installers only Orifice Identification Power Heat Duct Wall or Ceiling Mounting Optional Equipment for qualified installers only Wiring Diagram Follow the directions below to wire the blower box Modulating Remote Installation Maintenance Instructions6Index