Installation (for qualified installers only) | 2 1 |
Termination Requirements (see the illustration below)
!Venting terminals shall not be recessed into a wall or siding.
A Minimum 9" clearance from any door or window
B Minimum 12" above any grade, veranda, porch, deck or balcony
C Minimum 12" from outside corner walls
D Minimum 12" from inside corner walls
E Minimum 11" clearance below unventilated soffits or roof surfaces
Minimum 18" clearance below ventilated soffits
Minimum 6" clearance from roof eaves
NOTE: Vinyl surfaces require 24"
FMinimum 18" clearance below a veranda, porch, deck or balcony (must have two open sides)
GMinimum 48" clearance from any adjacent building
HMinimum 84" clearance above any grade when adjacent to public walkways or driveways NOTE: may not be used over a walkway or driveway shared by an adjacent building
IMinimum 48" clearance from any mechanical air supply inlet
JMinimum 36" clearance above and 48” below and to the sides of
KMinimum 36" from the area above the meter/regulator (vent outlet)
LMinimum 36" from the meter/regulator (vent outlet)
MMinimum 12” above the roof line (for vertical terminations)
NMinimum 24” horizontal clearance to any surface (such as an exterior wall) – for vertical terminations
Roof Eaves
E
N
M
E
A
K
G A
F
D C I
L
B
NOTE: Measure clearances to the nearest edge of the exhaust hood.
E
J
H
•Use the vinyl siding standoff (#1250) when installing on an exterior with vinyl siding.
•Vent termination must not be located where it will become plugged by snow or other material
•These clearances meet