FireplaceXtrordinair 44 DV XXL EF manual Vent Installation, Vertical Vent Requirements

Page 15

Installation (for qualified installers only)

1 5

Vent Installation

In addition to the requirements below, follow the requirements provided with the vent.

Vertical Vent Requirements

Vertical Termination (part # 1291)

Use a roof flashing and storm collar

whenever passing through the roof Combustible Framing

Use the Simpson ceiling firestop (#1263) whenever passing through a ceiling (or enclosure and at every floor penetration.

10"

by

10"

Min. 1" clearance from vertical sections to combustible surfaces.

Minimum framing for fire stop

Horizontal Vent

Requirements

Minimum framing

for fire stop

Minimum

12" tall

Minimum 10" wide

Use the Travis firestop (part # 93006094) when passing through a wall. NOTE: make sure the firestop is postitioned correctly so the 3" clearance is allowed above the vent.

1" Min.

Combustible

Surfaces

3" Min.

1" Min.

Slide the vent sections together and turn 1/4 turn until the sections lock in

place.

Screws are not required to secure the vent. However, three screws may be used to secure vent sections together if desired.

High temperature sealant is recommended at the appliance starter section

connection (use high-temperature silicone or Mill-Pac® ).

If disassembly is required, at time of re-assembly check to see if the vent creates a tight fit. If it does not, apply high temperature sealant to the joints of the affected sections.

Horizontal sections require a 1/4" rise every 12" of travel

Horizontal sections require non-combustible support every three feet (e.g.: plumbing tape)

Travis Industries

4050114

1 0 0 - 0 1 1 4 9

Image 15
Contents DV XXL EF Manual Travis Industries 4050114 0 0 1 1 4 IntroductionIntroduction Important InformationSafety Precautions 4050114 0 0 1 1 4 Travis Industries If YOU Smell GASThis Manual Features and Specifications Features Installation OptionsHeating Specifications Natural Gas Propane Installation Warnings Packing ListAdditional Items Required Recommended Installation Procedure Installation OverviewMinimum Framing Dimensions Fireplace Placement RequirementsVertical Standoff ClearancesRaised Fireplaces Corner Installations Gas Inlet Pressure Gas Line Requirements Fuel Gas Line ConnectionFireplace junction box Electrical ConnectionHorizontal Runs Vent RequirementsAltitude Considerations Part Numbers for 8 Diameter VentVertical Vent Requirements Vent InstallationMeasuring Vent Lengths Approved Vent ConfigurationsRestrictor Position ElbowsZero or Two 45 Offsets Four 45 Offsets Vertical Terminations with 0, 2, or 4 45 OffsetsHorizontal Terminations with One Vertical Elbow Horizontal Terminations with Three Vertical Elbows Vertical Terminations with Two Vertical 90 Elbows Termination Requirements see the illustration below Floor Mounted Fireplaces Hearth RequirementsMinimum Top Facing Clearance Facing RequirementsModifying the Face Angle for Rectangular Faces Face DimensionsFireplace Facing Detail Fireplace Facing Example Facing Under 1 ThickArched Faces Facing Example Facing Over 1 ThickMantel Requirements Combustible or Non-Combustible MantelsMinimum Mantel Clearance Arch Covers both sides Re-Attaching the Glass FrameGlass Frame Removal and Installation Place the Rear Log Place the Middle Logs Placing the Front Log Placing the Twigs Correct Arch Faces Architectural Faces Before You Begin Location of Controls See explanation below Operation3Starting The Pilot Flame 8OperationAdjusting the Flame Height Starting the Fireplace for the First TimeTurning the Fireplace On and Off Normal Operating Sounds Adjusting the Blower SpeedOptional Power Heat Duct 0OperationMaintaining Your Fireplaces Appearance Yearly Service ProcedureTroubleshooting Table MaintenanceHow this Fireplace Works What Turns the Main Burners On and OffWhat Prevents Gas Buildup Replacement Parts List Wiring DiagramFireplace Xtrordinair 44DVXXL Safety LabelYears 6 & 7 Coverage Parts only 6Limited 7 Year WarrantyYears 1 & 2 Coverage Parts & Labor Years 3 Through 5 Coverage Parts & LaborLP Conversion Instructions Burner ReplacementOptional Equipment for qualified installers only Orifice Identification Power Heat Duct Wall or Ceiling Mounting Optional Equipment for qualified installers only Wiring Diagram Follow the directions below to wire the blower box Maintenance Instructions Modulating Remote Installation6Index