INSTALLATION
Horizontal Venting with Two (2) 90o Elbows
INSTALLATION
One 90o elbow = Two 45o elbows.
Option |
| V | H + H1 | With these options, maximum total | |
A) | 2' | Min. | 4' Max. | pipe length is 30 feet with minimum | |
|
|
|
| of 6 feet total vertical and maximum | |
B) | 3' | Min. | 5' Max. | ||
8 feet total horizontal. | |||||
C) | 4' | Min. | 6' Max. | ||
| |||||
D) | 5' | Min. | 7' Max. | Please note minimum 1 foot | |
E) | 6' Min. | 8' Max. | between 90o elbows is required. |
VENT RESTRICTOR SETTING:
Vent restrictor must be at Set 0 for both NG and LP.
Horizontal Venting with Three (3) 90o Elbows
One 90o elbow = Two 45o elbows.
Option V | H | V + V1 H + H1 |
A)2' Min. 1' Max. 3' Min. 2' Max.
B)2' Min. 2' Max. 5' Min. 4' Max.
C)3' Min. 2' Max. 7' Min. 5' Max.
D)4' Min. 3 Max. 9' Min. 6' Max.
E)5' Min. 4' Max. 10' Min. 7' Max.
F)6' Min. 6' Max. 11' Min. 9' Max.
With these options, max. total pipe length is 30 feet with min. of 11 feet total vertical and max. 9 feet total horizontal.
Please note min. 1 foot between 90o elbows is required.
VENT RESTRICTOR SETTING:
Vent restrictor must be at Set 0 for both NG and LP.
20 | Regency® L676 Direct Vent Gas Fireplace |