Regency L676 Heat Release KIT, Hearth Requirements, Locating Your GAS Fireplace

Page 8

INSTALLATION

INSTALLATION

11)Install standard and optional features. Refer to the following sections:

a)Interior Brick Panels

b)Log Set

c)Exterior Brick Panels

d)Remote Control - refer to "Matching Remote Handset & Control Box ID Code" section.

12)Final check.

Before leaving this unit with the customer, the installer must ensure that the appliance is fi ring correctly and operation fully explained to customer.

This includes:

1)Clocking the appliance to ensure the correct fi ring rate (rate noted on label 42,000 (NG) Btu/h, 40,000 (LP) Btu/h) after burning appliance for 15 minutes.

2)If required, adjusting the primary air to ensure that the fl ame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.

CAUTION: Any alteration to the product that causes sooting or carboning that results in damage is not the responsibility of the manufacturer.

A) Flat on Wall

B) Flat on Wall Corner

C) Recessed into

Wall/Alcove

D) Corner

Diagram 1

4)This appliance is Listed for bedroom installations using the standard FireWizard Remote (millivolt thermostat system). Some areas may have further requirements, check local codes before installation.

5)The L676 Direct Vent Gas Fireplace is approved for alcove installations, see "Clearances" section for details.

6)We recommendthatyouplanyourinstallation on paper using exact measurements for clearances and floor protection before actually installing this appliance. Have an authorized inspector, dealer, or installer review your plans before installation.

HEAT RELEASE KIT

The Heat Release Kit expels warm air from the

replace to the outside of the building, allowing the fireplace to be operated with less heat entering the room. The kit may be used on either the left or right side.

SeeHeatReleaseinstallationmanualforcomplete details and clearances from side only.

HEARTH

REQUIREMENTS

Aminimum 29-1/8" (737mm) wide x 12" (305mm) deep x 2" (51mm) thick non-combustible hearth is required if the fi nished fl oor is not fl ush with the base of the unit. The maximum height between the fi nished fl oor and sub-fl oor is 1" (25mm).

MANUFACTURED

MOBILE HOME

ADDITIONAL

REQUIREMENTS

1)Ensure that structural members are not cut or weakened during installation.

2)Ensure proper grounding using the #8 ground lug provided. See "Wiring Diagram" section.

LOCATING YOUR

GAS FIREPLACE

1)When selecting a location for your fi replace, ensure that the clearances are met.

2)The appliance must be installed on a fl at, solid, continuous surface (e.g. wood, metal, concrete). This may be the fl oor, or raised up on a platform to enhance its visual impact. The appliance must be installed on a metal or wood panel extending the full width and depth of the appliance.

3)The L676 Direct Vent Gas Fireplace can be installed in a recessed position or framed out into the room as in A, B, C and D. See Diagram 1.

Note: For vent terminations refer to "ExteriorVent TerminationLocations" section.

HEATWAVE

DUCT KIT

The HeatWave Air Duct Kit increases the effectiveness of your fi replace by dispersing warm air from the fi replace to remote locations in the same room or other rooms in your home.

Up to two kits may be installed on the fi replace. Please Note: Only 1 HeatWave kit may be operated at one time.

See HeatWave installation manual for complete details and clearances from side only.

The HeatWave Duct Kit has different clearance and framing requirements, check the HeatWave manual for details.

NOTE: No hearth is required when the unit is fl ush with the fi nished fl oor as shown below.

The minimum fl oor clearance must be maintained from the top surface of the carpet, etc. to the unit base.

8

Regency® L676 Direct Vent Gas Fireplace

Image 8
Contents Libertytm L676 Gas Fireplace Manufactured Mobile Home Requirements Table of Contents Safety Label Copy of Safety DecalRequirements MA Code CO DetectorUnit Dimensions Installation General Safety InformationInstallation Checklist Important Message Save These InstructionsHeat Release KIT Hearth RequirementsManufactured Mobile Home Additional Requirements Locating Your GAS FireplaceClearances Mantel Clearances Mantel LEG ClearancesFraming & Finishing Important Header must be metal studUnit Assembly Prior to InstallationVenting Introduction Vent Restrictor PositionFactory set for NG units Factory set for LP unitsExterior Vent Termination Requirements Venting Arrangements FPI Kit # Length ContainsInstallation Rigid Pipe Venting Systems8 Rigid Pipe Cross Reference Chart 58DVA-16ABL676 & L900 Direct Vent Fireplace Allowable Horizontal Terminations Horizontal Venting with Two 2 90o Elbows Vertical Venting with Two 2 90o Elbows Vent must be supported at offsets Feet HeightUnit Installation with Horizontal Termination Unit Installation With Vertical Termination This allows for small adjustmentsDiagram Minimum VentUnit Installation Horizontal Termination with Flex Vent SystemGAS Line BACK-UP Battery Installation Hinge Door Heat Shield Power ModulePower Module Heat Shield Latch LocationConversion KIT #521-969 from NG to LP Clip Heat Shield Using a flat head screw driverPilot ShieldHeat J9 Jumper Location J9 JumperHeat Shield Front Burner Bracket Heat Shield Front Burner RemovedHinge Door Rear Log Stand GrateModulating Coil Wires Bottom Brick PanelHeat Shield Bracket Heat ShieldCable Tie Pilot ShieldClip Brick Panel Installation Handle with care. do not Force Into PositionOuterbox of Firebox Bracket Brick Panel Clip Tab Base Brick Panel SlotBackside of Grate LOG SET InstallationRear Burner Tube Front Burner Tube Complete Log Set Installation Aeration Adjustment Wiring DiagramLighting Procedure Operating InstructionsMatching Remote Handset & Control BOX ID Code Operating InstructionsNormal Operating Sounds GAS Appliances Shutdown ProcedureOperation During Power Outage GAS Control Valve Copy of Lighting Plate InstructionsRight Side Exterior Brick Panel Heat ShieldMaintenance BACK-UP Battery Replacement Bracket Hinge Heat DoorPower Module Replacement Bracket Heat ShieldControl Module Control Module ReplacementBracket Hinge Heat Heat Shield Replace the DC sparker DC Sparker ReplacementBattery Cover Valve Tray Replacement Unplug the power sourceModulating coil Carefully remove the bottom brick panelValve Description Parts ListMain Assembly Parts List Burner & LOG Assembly Parts List Parts List Parts List Warranty Warranty Limited LifetimeInstaller Please complete the following information