GENERATOR START-UP PROCEDURE (MANUAL MODE)
BEFORE STARTING
CAUTION
The engine’s exhaust contains harmful emissions.
ALWAYS have adequate ventilation when operating. Direct exhaust away from nearby personnel.
WARNING
NEVER manually start the engine with the main, GFCI or auxiliary circuit breakers in the ON (closed) position.
1.Place the main, G.F.C.I., and aux. circuit breakers (Figure 37) in the OFF position prior to starting the engine.
Figure 37. Main, Aux. and GFCI
Circuit Breakers (OFF)
2.Make sure the voltage
3.Connect the load to the receptacles or the output terminal lugs as shown in Figure 12. These load connection points can be found on the output terminal panel and the output terminal panel’s hard wire hookup panel.
4.Tighten terminal nuts securely to prevent load wires from slipping out.
5.Close all engine enclosure doors (Figure 38).
CORRECT INCORRECT
Figure 38. Engine Enclosure Doors
STARTING
1.Place the voltage selector switch in the desired voltage position (Figure 39)..
Figure 39. Voltage Selector Switch
STARTING (MANUAL)
1.Place the engine speed switch (Figure 40) in the LOW (down) position.
Figure 40. Engine Speed Switch (Low)
2.Place the MPEC control switch in the MANUAL position to start the engine (Figure 41).
Figure 41. MPEC Control Switch
(Manual Position)
3.Depending on the temperature of the coolant (cold weather conditions), the
Figure 42. Pre-Heat Lamp
PAGE 50 — DCA85USJ2 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/22/11)