Multiquip DCA85usJ2 Outdoor Installation, Indoor Installation, Mounting, Generator Grounding

Page 15

INSTALLATION

OUTDOOR INSTALLATION

Install the generator in a area that is free of debris, bystanders, and overhead obstructions. Make sure the generator is on secure level ground so that it cannot slide or shift around. Also install the generator in a manner so that the exhaust will not be discharged in the direction of nearby homes.

The installation site must be relatively free from moisture and dust. All electrical equipment should be protected from excessive moisture. Failure to do will result in deterioration of the insulation and will result in short circuits and grounding.

Foreign materials such as dust, sand, lint and abrasive materials have a tendency to cause excessive wear to engine and alternator parts.

CAUTION

Pay close attention to ventilation when operating the generator inside tunnels and caves.The engine exhaust contains noxious elements. Engine exhaust must be routed to a ventilated area.

INDOOR INSTALLATION

Exhaust gases from diesel engines are extremely poisonous. Whenever an engine is installed indoors the exhaust fumes must be vented to the outside. The engine should be installed at least two feet from any outside wall. Using an exhaust pipe which is too long or too small can cause excessive back pressure which will cause the engine to heat excessively and possibly burn the valves.

MOUNTING

The generator must be mounted on a solid foundation (such as concrete) and set fi rmly on the foundation to isolate vibration of the generator when it is running.The generator must set at least 6 inches above the fl oor or grade level (in accordance to NFPA 110, Chapter 5-4.1). DO NOT remove the metal skids on the bottom of the generator. They are to resist damage to the bottom of the generator and to maintain alignment.

GENERATOR GROUNDING

To guard against electrical shock and possible damage to the equipment, it is important to provide a good EARTH ground.

Article 250 (Grounding) of the National Electrical Code (NEC) provides guide lines for proper grounding and specifi es that the cable ground shall be connected to the grounding system of the building as close to the point of cable entry as practical.

NEC articles 250-64(b) and 250-66 set the following grounding requirements:

1.Use one of the following wire types to connect the generator to earth ground.

a.Copper - 8 AWG (5.3 mm2)

b.Aluminum - 6 AWG (8.4 mm2)

2.When grounding the generator (Figure 2) connect the ground cable between the lock washer and the nut on the generator and tighten the nut fully. Connect the other end of the ground cable to earth ground.

3.NEC article 250-52(c) specifies that the earth ground rod should be buried a minimum of 8 ft. into the ground.

NOTICE

When connecting the generator to any buildings electrical system ALWAYS consult with a licensed electrician.

DCA85USJ2 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/22/11) — PAGE 15

Image 15
Contents This Manual Must Accompany the Equipment AT ALL Times Model DCA85USJ2Proposition 65 Warning Administrator Reporting Safety DefectsDCA-85USJ2 Generator Table of ContentsOrdering parts has never been easier Parts Ordering ProceduresSafety Messages Safety InformationGeneral Safety Generator Safety Always know the location of the nearest Before servicing equipment Engine SafetyFrom fuel vapors or if fuel is spilled on a hot engine Fuel SafetyTowing Safety  Never use fuel as a cleaning agentDevice. All installations should be Electrical SafetyGrounding Safety Power Cord/Cable SafetyEnvironmental Safety Battery SafetyDCA-85USJ2 SpecificationsDimensions DimensionsTypical Generator Grounding Application InstallationGenerator Grounding Outdoor InstallationIndoor Installation MountingGeneral Information Item no Major ComponentsDiagnostic Display Display ParametersMenu Button Press this button to enter or exit menu screens First Time Start Up Main Menu NavigationSelecting a Language Engine Configuration Data Stored Fault CodesFirst Time Start-Up Touch the Menu Button to return to the main menu Faults and Warning Auxiliary Gage FaultDisplay will return to the single or four parameter screen Fault Code Active Fault CodesShutdown Codes Bachlight AdjustmentContrast Adjustment Select Units Setup 1-UP DisplayUSE Defaults Automatic Scan on Setup 4-Up Display Select the 4-Up Custom Setup from the 4-Up Setup menuTouch the Enter Button and a list of parameters will appear Functions Utilities information and troubleshootingTouch Menu Button to return to the Utilities menu When fi nished, touch Menu to return to the previous screen Modbus SetupNo Data Data ErrorTimeout ECU not Responding Canbus FailureOFF Generator Control PanelOFF Engine Operating PanelEngine Operating Panel Output Terminal Panel Familiarization Output Terminal FamiliarizationTerminal legs O and Ground are considered bonded grounds VAC Gfci Receptacles Removing the Plastic Face Plate Hard Wire Hookup PanelOver Current Relay Connecting LoadsSingle Phase Load Three Phase LoadLoad Application Generator Output Voltages Generator OutputsAC Ammeter Gauge Reading HOW to Read the AC Ammeter and AC Voltage GaugesGenerator OUTPUTS/GAUGE Reading AC Voltmeter Gauge Reading3Ø-208V/1Ø-120V Uvwo Terminal Output Voltages Output Terminal Panel ConnectionsUvwo Terminal Output Voltages 3Ø-240/139 Uvwo Terminal Output Voltages1Ø-240/120V Uvwo Terminal Output Voltages 3Ø-480/277V Uvwo Terminal Output VoltagesFuel Check INSPECTION/SETUPCircuit Breakers Lubrication OILOnly use #2 diesel fuel when refueling Refueling ProcedureOperation in Freezing Weather Cleaning the RadiatorAIR Cleaner FAN Belt Tension Coolant ANTIFREEZE/SUMMER COOLANT/ WaterAlternator BatteryBattery Cable Installation WiringStarting Manual Generator START-UP Procedure Manual ModeBefore Starting StartingEngine Speed Switch High Starting Auto Mode Before connecting this generator to anyWithout this transfer switch Generator SHUT-DOWN Procedures Normal Shutdown ProcedureEmergency Shutdown Procedure Maintenance General Inspection AIR CleanerAir Cleaner with Dust Indicator Fuel Addition Fuel Tank InspectionAIR Removal Flushing OUT Radiator and Replacing Coolant Radiator CleaningCheck OIL Level Replacing Oil FilterTrailer Maintenance Trailer MaintenanceCoupler Type of hitch used on the trailer for towing Actuator Brake AdjustmentBrakes Hydraulic Surge BrakesTIRES/WHEELS/LUG Nuts Tire Wear/InflationSuspension Never use an pneumatic air gun to tighten wheel lug nuts Lug Nut Torque RequirementsTrailer/Towing Vehicle Wiring Diagram Trailer Wiring DiagramGenerator Wiring Diagram Generator Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramTroubleshooting Generator Adjust governor controller Troubleshooting Engine ControllerClean/repair radiator grill Adjust governor actuatorExplanation of Code in Remarks Column Sample Parts ListTo 3 units Suggested Spare PartsGenerator Assy 8101015003 81010700330012810035 8101611004Control BOX Assy 0330000280 M2213001702M2213001712 0330000180Control BOX Assy 33B 0601802149 M42666000040601802218 33A 0601806653Control BOX Assy 0080200007 M32231000040027105010 M9220100004Engine and Radiator Assy RE529643 M2923200094R135680 RE504836Engine and Radiator Assy 0603306399 06055113950605511399 0603306395Output Terminal Assy 0039316000 M3230700003M9220100304 M9220100404Battery Assy 0602220920 0602220199M9310500014 M9103000304Muffler Assy M2333200204 M23301013030017112030 M2333001603Fuel Tank Assy 0605516090 M23630009020605505070 0605501073Enclosure 1 Assy 0603306797 M2413002202M2363300703 0016910030Enclosure 1 Assy M2423200814 M246320060334A M2493502104 M2463400203Enclosure 2 Assy M2443400003 M3443001902M3493308603 M3443002004Enclosure 2 Assy M9110100904 29A C931250000430A 0030006000 M9110100804Rubber Seals Assy 0229200125 02292012400229201130 0314502550Nameplate and Decals Assy M2550002613 M1550000204M1550002203 M2550002603Freight Policy Terms and Conditions of Sale PartsPage HERE’S HOW to GET Help