Replacement CM 4000
K−4 CM 4000 Installation and Operating Manual
7. To verify that the replacement unit is ready for use:
a. Go to “JNS Applications > Control Center > Bootp” and check that the correct MAC address is being used for the
replacement CM. Also go to the “TFTP Status” tab and look for an indication that the “transfer succeeded” (“100%
complete”). If these indications are correct, proceed as follows:
b. Swap control to the replacement CM 4000 by pressing the Activate button.
c. Confirm system operation.
d. Assuming all is well leave the replacement CM 4000 in control of the system. The installation is now complete.
Should problems be experienced return control immediately to the opposite CM 4000. De−power the r eplacement CM 4000,
check all cabling, and reapply power. Should this fail to eliminate the fault, it may be necessary to download a new configura-
tion set; refer to “Validating, Compiling, and Activating (Downloading) a Configuration Set” on page 5−13.
If problems persist, contact Grass Valley Technical Support.