Chapter 3: Provisioning

September 25, 2006

Modem Parameters (Configure and Test Dial-out Alarm Reporting)

In the Config menu, press M to display the Modem Parameters menu (Figure 3-7). This menu is used to configure the EMUs modem parameters for autonomous dial-out reporting of alarms to a remote management station or printer.

 

Figure 3-7. Modem Parameters Menu

 

Note: Connect and configure the shelf modem as instructed in “Remote Terminal and Local Shelf Modem

 

Connections” on page 2-7.

 

 

Step

Action

1

Navigate the menu using the Ç and È arrow keys on the keyboard.

 

 

2

Use the SPACEBAR to toggle the Data Bits field to "7" or "8" (to match modem at remote management

 

station).

 

 

3

Toggle the Parity Bit field to "NONE," "ODD," or "EVEN" (to match modem at remote management

 

station).

 

 

4

Toggle the Stop Bit field to "1" or "2" (to match modem at remote management station).

 

 

5

Toggle the Baud Rate field to the appropriate setting (to match modem at remote management station).

 

 

6

In the Phone Number field, enter the phone number of the modem at the remote management station.

 

Note: The Phone Number field must be preceded by "atdt" for tone dialing or "atdp" for pulse

 

dialing.

 

The Init String field displays "ATE1Q0." This is the default Hayes compatible modem

 

initialization string. If you need to change this initialization string, consult your modem user

 

manual or call the ADC Technical Assistance Center at the number listed on page B-1.

 

 

7

Press ENTER to confirm settings and return to the top of the Config menu.

 

 

3-14

LTPE-UM-3159-02

Page 46
Image 46
ADC EMU-830 user manual Modem Parameters Configure and Test Dial-out Alarm Reporting, Modem Parameters Menu