September 25, 2006 | Chapter 3: Provisioning | |
To configure the shelf alarms: |
| |
|
|
|
Step | Action |
|
1 | Navigate the menu using the Ç and È arrow keys on the keyboard. |
|
|
| |
2 | In the Loss of power on one 48V supply field, use the SPACEBAR to select DIS (disabled), MIN | |
| (minimum), MAJ (major), or CRT (critical). |
|
|
| |
3 | In the HDSL alarm if 3 lines down field, use the SPACEBAR to select DIS (disabled), MIN (minimum), | |
| MAJ (major), or CRT (critical). |
|
|
| |
4 | In the Loss of External Clock field (on | |
| (disabled), MIN (minimum), MAJ (major), or CRT (critical). |
|
|
| |
5 | In the ACO Retirement of Alarm Relays field, use the SPACEBAR to select DIS (disabled) or ENA | |
| (enabled) for the Audible and Visual fields of the Critical, Major, and Minor alarm relays. | |
|
|
|
6 | Press ENTER to confirm settings and return to the top of the Config menu. |
|
|
|
|
Remote Alarm Reporting
This Config menu option (Figure
Figure 3-11. Remote Alarm Reporting Menu Item
Set Date and Time
Use the Æ arrow key to select Config, then press D to display the Set Date/Time dialog box (Figure
The Date format is DD/MM/YYYY (day/month/year). The Time format is HH:MM:SS (hour:minute:second) and displays as a
Note: Setting the EMU’s date and time automatically sets the date and time for all HDSL/G.SHDSL cards in the shelf.
|