10kVA 400V UPS

IS10KH

Performance - Linear Load

DC to AC Efficiency [%]

87.0

AC to AC Efficiency [%]

83.0

Heat Dissipation [BTU/h] [W]

6,003/1,758

 

 

Electrical Input

 

 

 

 

 

Mains

 

Voltage

400 V 3 Wire + G

P Nom.

10.3 kW

I Nom.

17.7 A

(Nominal input current based on nominal mains

 

voltage and batteries fully charged at 100% ohmic

 

load)

 

I Max.

19.9 A

(Maximum input current based on full battery

 

recharge and nominal mains voltage at 100% ohmic

 

load)

 

Over-Current protection [A]

20 A

(Based on continuous full load)

 

Input Voltage Range

+ 10%, -15% programmable

Input Frequency

50 Hz + 6% programmable

Current Distortion

< 12%

Power Factor

0.8 - 0.9

Bypass

 

Voltage

400 V 3 Wire + N + G

I Nom

14.4 A

Over-Current protection [A]

15 A

(Based on continuous full load)

 

Bypass Voltage Range

+ 10% programmable

 

 

Electrical Output

 

 

 

 

 

Voltage

400 V 3 Wire + N + G

Nominal Current

14.4 A

(The output Current is based on the nominal apparent

 

power of the UPS)

 

Frequency Range

50Hz (adjustable 0.25, 0.50, 1-8%)

 

 

990-2440

AIS 5000 400V Installation Manual

24

Page 30
Image 30
American Power Conversion AIS 5000 manual 10kVA 400V UPS