Programming and Set-Up - Operation Modes

Normal to Manual Bypass Operation

CAUTION!

Never operate the manual bypass switch when the UPS is in normal operation.

Caution

Press and the cursor keys or until the display shows:

Press . If the bypass mains is within tolerance range, the UPS will transfer to electronic bypass. The display shows:

Make sure that the Bypass Static Switch is turned on.

Switch on the Manual Bypass Switch (Q050).

Bypass Operation:

OFF

Bypass Operation

Standby

Switch off the Output Breaker Q100.

Push the S002 button on the front panel in order to turn the UPS off. The UPS changes to standby operation. Display shows:

Switch off the Q090, Q001 and Q004 breakers.

Wait 30 seconds until the UPS display and all LED indications are switched off.

The load is now supplied directly from the bypass mains.

Note

CAUTION!

When the UPS is in bypass operation, the load support will be disrupted if the bypass Caution mains fails.

990-2440

AIS 5000 400V Installation Manual

73

Page 79
Image 79
American Power Conversion AIS 5000 manual Normal to Manual Bypass Operation