80kVA 400V UPS

IS80KH

Performance - Linear Load

DC to AC Efficiency [%]

91.0

AC to AC Efficiency [%]

87.9

Heat Dissipation [BTU/h] [W]

29,809/8,728

 

 

Electrical Input

 

 

 

 

 

Mains

 

Voltage

400 V 3 Wire + G

P Nom.

72.33 kW

I Nom.

118.23 A

(Nominal input current based on nominal mains

 

voltage and batteries fully charged at 100% ohmic

 

load)

 

I Max.

152.8 A

(Maximum input current based on full battery

 

recharge and nominal mains voltage at 100% ohmic

 

load)

 

Over-Current protection [A]

160 A

(Based on continuous full load)

 

Input Voltage Range

+ 10%, -15% programmable

Input Frequency

50 Hz + 6% programmable

Current Distortion

< 12%

Power Factor

0.8 - 0.9

Bypass

 

Voltage

400 V 3 Wire + N + G

I Nom

115.5 A

Over-Current protection [A]

125 A

(Based on continuous full load)

 

Bypass Voltage Range

+ 10% programmable

 

 

Electrical Output

 

 

 

 

 

Voltage

400 V 3 Wire + N + G

Nominal current

115.5 A

(The output current is based on the nominal apparent

 

power of the UPS)

 

Frequency Range

50Hz (adjustable 0.25, 0.50, 1-8%)

 

 

44

AIS 5000 400V Installation Manual

990-2440

Page 50
Image 50
American Power Conversion AIS 5000 manual 80kVA 400V UPS, Mains Voltage 400 V 3 Wire + G Nom 72.33 kW 118.23 a, Max 152.8 a