American Power Conversion AIS 5000 manual External Connection 100kVA 400V UPS

Models: AIS 5000

1 82
Download 82 pages 5.69 Kb
Page 56
Image 56

External Connection - 100kVA 400V UPS

Communication and Management

Emergency Power Off (EPO)

Yes

 

 

Physical Values

 

 

 

 

 

Dimensions (H × W × D)

 

Unit

1,800 × 1,600 × 810 mm

Shipping

2,080 × 1,830 × 1,016 mm

Weight

 

Unit

1,500 kg

Shipping

1,575 kg

Max. Power Cable size [mm]

2 × 95

Recommended Cable sizes

 

Ext. Input Cable [mm]

70

Ground Cable [mm]

50

Ext. Output Cable [mm]

35

Ext. Battery Cable [mm]

2 × 95

Ext. Alarm Cable Max. [mm]

1.5

Recommended Conduit sizes

 

Input

2.50”

Output

1.25”

Battery

2 × 2”

Alarm

1/2”

 

 

Environmental Values

 

 

 

 

 

Temperature

 

Operating

0o - 40o C

Storage

-40o- 70o C

Elevation

 

Operating

0 - 1,000 m

Storage

0 - 5,000 m

Humidity

Max. 95% non-conditioned

Protection Class

IP30 (IP32 optional)

Transient Attenuation

Differential mode 60 to 80 dB, Common mode 120 dB

Audible Noise at 3.28 feet (1 m)

60-70 dB, depending on type

 

 

Compliance

 

 

 

 

 

Approvals

IEC 62040/EN 50091 Class A, VFI-SS-112

 

 

50

AIS 5000 400V Installation Manual

990-2440

Page 56
Image 56
American Power Conversion AIS 5000 manual External Connection 100kVA 400V UPS