Programming and Set-Up - Programming the UPS

Bypass Operation

Push

and the cursor keys

or

 

 

Bypass Operation:

 

until the display shows:

 

 

 

OFF

 

To select Bypass Operation, push

.

 

 

 

The UPS will switch to Bypass Operation if the

 

 

bypass mains is within the specified tolerance

Bypass Operation

 

range. The display will show:

 

 

 

 

The load is now supplied from the bypass mains through the static switch. Bypass mains voltage and output voltage will appear on the display.

To return to Normal Operation, push .

The UPS transfers from one operation mode to another without affecting the load.

Boost Charge

To program the UPS for Boost Charge, press

and browse through the menu, using

the cursor keys or .

The display shows:

Boost Charge:

OFF

 

Choose Boost Charge by selecting .

To deactivate, press .

When the Boost Charge function is selected, the UPS will remain in the Boost Charge operational mode for 8 hours. To change the boost charge operating time, contact APC. (The UPS can be programmed to stay in this mode for up to 24 hrs).

990-2440

AIS 5000 400V Installation Manual

63

Page 69
Image 69