External Connection - Connecting the UPS

Mounting the Conduit Box:

1.Open UPS front door.

2.Remove cover from the input/output section.

1

1

 

S001

 

S002

0

0

In order to remove the cover from the in- and output section, please remove all 8 M6×12 torx screws.

3.Place Conduit Box under UPS and align it with hole in UPS bottom plate.

4.Take out Conduit Box and make holes in Conduit Box according to below table.

Conduit sizes (mm):

 

Input Conduit

Output/Bypass

Battery

Alarm Conduit

 

Conduit

Conduit

 

 

 

 

 

 

 

 

10 kVA

12.7

12.7

12.7

12.7

 

 

 

 

 

20 kVA

19.05

12.7

25.4

12.7

 

 

 

 

 

30 kVA

25.4

19.05

31.75

12.7

 

 

 

 

 

40 kVA

25.4

25.4

38.1

12.7

 

 

 

 

 

60 kVA

31.75

25.4

63.5

12.7

 

 

 

 

 

80 kVA

38.1

31.75

2 × 38.1

12.7

 

 

 

 

 

100 kVA

38.1

31.75

2 × 50

12.7

 

 

 

 

 

14

AIS 5000 400V Installation Manual

990-2440

Page 20
Image 20