Programming and Set-Up - Programming the UPS

Battery Monitor Test

This parameter will only appear on the display, if the Advanced Battery Monitor option is installed.

To perform the Battery Monitor Test, push

and browse through the menu,

using the cursor keys

or

 

until

 

the display shows:

 

 

 

 

 

 

To perform a Battery Monitor Test,

select To deactivate, press .

The Battery Monitor Test checks the battery condition by switching off the rectifier, and running the inverter in battery operation until 25% of the battery capacity is used.

In the event of a battery failure, the rectifier will automatically switch on. There will be no output voltage loss.

If the battery condition is within the tolerance range, no alarms will appear on the display.

In case of reduced battery capacity, one of the following two alarms will appear on the display:

Battery Monitor Warning — means that the battery capacity is reduced by 25% or more.

Battery Monitor Alarm — no battery capacity or capacity is reduced by 50% or more.

Battery Monitor Test: OFF

Battery Monitor Warning

Battery Monitor Alarm

66

AIS 5000 400V Installation Manual

990-2440

Page 72