External Connection - 40kVA 400V UPS
38 AIS 5000 400V Installation Manual 990-2440
Emergency Power Off (EPO) Yes
Physical Values
Dimensions (H × W × D)
Unit 1,800 × 1,200 × 810 mm
Shipping 2,080 × 1,422 × 1,016 mm
Weigh t
Unit 900 kg
Shipping 950 kg
Max. Power Cable size [mm] 70
Recommended Cable sizes [mm]
Ext. Input Cable [mm] 16
Ground Cable [mm] 16
Ext. Output Cable [mm] 16
Ext. Battery Cable [mm] 70
Ext. Alarm Cable Max. [mm] 1.5
Recommended Conduit sizes
Input 1.25”
Output 1”
Battery 1.5”
Alarm 1/2”
Environmental Values
Temperature
Operating 0o - 40o C
Storage -40o - 70o C
Elevation
Operating 0 - 1,000 m
Storage 0 - 5,000 m
Humidity Max. 95% non-conditioned
Protection Class IP30 (IP32 optional)
Transient Attenuation Differential mode 60 to 80 dB, Common mode 120 dB
Audible Noise at 3.28 feet (1 m) 60-70 dB, depending on type
Compliance
Approvals IEC 62040/EN 50091 Class A, VFI-SS-112
Communication and Management