40kVA 400V UPS

IS40KH

Performance - Linear Load

DC to AC Efficiency [%]

90.8

AC to AC Efficiency [%]

87.0

Heat Dissipation [BTU/h] [W]

16,333/4,782

 

 

Electrical Input

 

 

 

 

 

Mains

 

Voltage

400 V 3 Wire + G

P Nom.

36.9 kW

I Nom.

61.93 A

(Nominal input current based on nominal mains

 

voltage and batteries fully charged at 100% ohmic

 

load)

 

I Max.

77.8 A

(Maximum input current based on full battery

 

recharge and nominal mains voltage at 100% ohmic

 

load)

 

Over-Current protection [A]

80 A

(Based on continuous full load)

 

Input Voltage Range

+ 10%, -15% programmable

Input Frequency

50 Hz + 6% programmable

Current Distortion

< 12%

Power Factor

0.8 - 0.9

Bypass

 

Voltage

400 V 3 Wire + N + G

I Nom

48.1 A

Over-Current protection [A]

60 A

(Based on continuous full load)

 

Bypass Voltage Range

+ 10% programmable

 

 

Electrical Output

 

 

 

 

 

Voltage

400 V 3 Wire + N + G

Nominal current

57.7 A

(The output current is based on the nominal apparent

 

power of the UPS)

 

Frequency Range

50Hz (adjustable 0.25, 0.50, 1-8%)

 

 

36

AIS 5000 400V Installation Manual

990-2440

Page 42
Image 42
American Power Conversion AIS 5000 manual 40kVA 400V UPS, Mains Voltage 400 V 3 Wire + G Nom 36.9 kW 61.93 a, Max 77.8 a