External Connection - Connecting the UPS

Terminals.

 

Input X001/Output

 

Protective Earth

 

X004/Bypass Input

Battery Q004

 

PE

 

X090

 

 

 

 

 

 

 

 

10 kVA

M6

Direct on breaker

Direct on Earth Busbar

 

 

terminals

 

 

 

 

 

20 kVA

M6

Direct on breaker

Direct on Earth Busbar

 

 

terminals

 

 

 

 

 

30 kVA

M6

Direct on breaker

Direct on Earth Busbar

 

 

terminals

 

 

 

 

 

40 kVA

M8

Direct on breaker

Direct on Earth Busbar

 

 

terminals

 

 

 

 

 

60 kVA

M8

Direct on breaker

Direct on Earth Busbar

 

 

terminals

 

 

 

 

 

80 kVA

M10

Direct on breaker

Direct on Earth Busbar

 

 

terminals

 

 

 

 

 

100 kVA

M10

Direct on breaker

Direct on Earth Busbar

 

 

terminals

 

 

 

 

 

The UPS input / bypass input is 4-Wire + Ground.

Note

Torque specifications.

Stud size

6 mm

8 mm

10 mm

12 mm

 

 

 

 

 

Torque

66/7.5 lb-in/Nm

133/15 lb-in/Nm

266/30 lb-in/Nm

443/50 lb-in/Nm

 

 

 

 

 

Grounding

System grounding:

Grounding busbar marked “Grounding” must be connected by grounding electrode conductor to a local grounding electrode. Grounding electrode conductor to be supplied by the customer. (See grounding busbar on illustrations starting on page 17).

20

AIS 5000 400V Installation Manual

990-2440

Page 26
Image 26
American Power Conversion AIS 5000 manual Grounding, X090