990-2440 AIS 5000 400V Installation Manual 69
Setting stack
In the setting stack, the following parameters are changeable:
Parameter Factory Setting
Normal Charge Voltage 272 Vdc
Boost Charge Voltage 272 Vdc - no boost required
Charge Current Max. Refer to below tab le
Low Battery Warning 216 Vdc
Low Battery Shutdown 204 Vdc
Boost Charge Time 8 hours
Slew rate 0 – 4 1 Hz
Charger ON/OFF ON
Inverter and Bypass ON/OFF ON
Battery Back-up Time Until a battery capacity test has been
performed, display will show xxx
High Battery Temperature 35oC
Auto Battery Monitor ON
Battery Summary Error OFF
Remote Shutdown OFF
Remote Shutdown Polarity HIGH
Remote Shutdown Time 2 minutes
Max. Charge Current
UPS ADC
10 kVA 5
20 kVA 10
30 kVA 15
40 kVA 20
60 kVA 30
80 kVA 40
100 kVA 50