Setting stack

In the setting stack, the following parameters are changeable:

 

Parameter

Factory Setting

 

 

 

 

Normal Charge Voltage

272 Vdc

 

 

 

 

Boost Charge Voltage

272 Vdc - no boost required

 

 

 

 

Charge Current Max.

Refer to below table

 

 

 

 

Low Battery Warning

216 Vdc

 

 

 

 

Low Battery Shutdown

204 Vdc

 

 

 

 

Boost Charge Time

8 hours

 

 

 

 

Slew rate 0 – 4

1 Hz

 

 

 

 

Charger ON/OFF

ON

 

 

 

 

Inverter and Bypass ON/OFF

ON

 

 

 

 

Battery Back-up Time

Until a battery capacity test has been

 

 

performed, display will show xxx

 

 

 

 

High Battery Temperature

35oC

 

Auto Battery Monitor

ON

 

 

 

 

Battery Summary Error

OFF

 

 

 

 

Remote Shutdown

OFF

 

 

 

 

Remote Shutdown Polarity

HIGH

 

 

 

 

Remote Shutdown Time

2 minutes

 

 

 

 

 

 

 

Max. Charge Current

 

 

 

 

 

UPS

ADC

 

10 kVA

5

 

 

 

 

20 kVA

10

 

 

 

 

30 kVA

15

 

 

 

 

40 kVA

20

 

 

 

 

60 kVA

30

 

 

 

 

80 kVA

40

 

 

 

 

100 kVA

50

 

 

 

990-2440

AIS 5000 400V Installation Manual

69

Page 75
Image 75
American Power Conversion AIS 5000 manual Setting stack, Minutes, kVA 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA