External Connection - 10kVA 400V UPS

Electrical Output

 

 

 

 

 

 

 

Frequency Regulation

50 Hz, + 0.1% free running

Output Voltage Range

100% static symmetrical load + 1%, 100% static asymmetrical load

 

+ 3%, no load to full load + 4%

Output Harmonic Distortion

<3% linear load <5%

Load Crest Factor

5: 1

 

Load Power Factor

0.9 leading to 0.7 lagging

Overload Capacity

150% for 1 min., 125% for 10 min., Bypass Operation 1000% for 5

 

cycles

Connection Type

3 PH + N + G

 

 

 

Battery - External Only

 

 

 

 

 

 

 

Nominal Voltage

240 V

(Nominal battery voltage assumed to be 2.0 V/cell

 

 

(lead technology)

 

 

Number of Battery Cells

120

 

Float Charge Voltage

272 Volt DC programmable

Charge Voltage Range

100 to 115% of the DC nominal Voltage, + 1% IU characteristic

Low Battery Warning Range

210-222 Vdc (Factory Setting 210 V)

Low Battery Shutdown

204 Vdc

Full Load (P)

9.2 kW

(The battery power takes in to account the DC-AC

 

 

efficiency of the main inverter for linear load)

 

 

Recommended Breaker Size [A]

60 A

Connection Type

Hard Wire 3-wire (DC+/- + G)

Nominal Discharge Current [A]

38 A

(The battery nominal discharge current is based on

 

 

the nominal cell Voltage of 2.0 V/cell - number

 

 

of cells = 120 which gives a total Voltage of 240V)

 

 

Max. Discharge Current [A]

46 A

(The battery max. discharge current is based on a cell

 

 

end Voltage of 1.70V/cell which gives a total Voltage

 

 

of 204V)

 

 

 

 

 

Communication and Management

 

 

 

 

 

 

 

Control Panel

Multi-function LCD status and control console

RS232 Port

Yes

Network Management Card 10/100

Yes

Base T

 

 

Audible Alarm

Audible and visible alarms prioritized by severity

Slots Empty

1

 

Modbus/BMS Card

Optional

 

 

 

990-2440

AIS 5000 400V Installation Manual

25

Page 31
Image 31
American Power Conversion AIS 5000 manual Nominal Voltage 240, Max. Discharge Current a 46 a