20kVA 400V UPS

IS20KH

Performance - Linear Load

DC to AC Efficiency [%]

89.0

AC to AC Efficiency [%]

85.3

Heat Dissipation [BTU/h] [W]

9,923/2,905

 

 

Electrical Input

 

 

 

 

 

Mains

 

Voltage

400 V 3 Wire + G

P Nom.

19.88 kW

I Nom.

33.79 A

(Nominal input current based on nominal mains

 

voltage and batteries fully charged at 100% ohmic

 

load)

 

I Max.

39.4 A

(Maximum input current based on full battery

 

recharge and nominal mains voltage at 100% ohmic

 

load)

 

Over-Current protection [A]

40 A

(Based on continuous full load)

 

Input Voltage Range

+ 10%, -15% programmable

Input Frequency

50 Hz + 6% programmable

Current Distortion

< 12%

Power Factor

0.8 - 0.9

Bypass

 

Voltage

400 V 3 Wire + N + G

I Nom.

28.9 A

Over-Current protection [A]

30 A

(Based on continuous full load)

 

Bypass Voltage Range

+ 10% programmable

 

 

Electrical Output

 

 

 

 

 

Voltage

400 V 3 Wire + N + G

Nominal Current

28.9 A

(The output Current is based on the nominal apparent

 

power of the UPS)

 

Frequency Range

50Hz (adjustable 0.25, 0.50, 1-8%)

 

 

28

AIS 5000 400V Installation Manual

990-2440

Page 34
Image 34
American Power Conversion AIS 5000 manual 20kVA 400V UPS, Mains Voltage 400 V 3 Wire + G Nom 19.88 kW 33.79 a, Max 39.4 a