Environmental Requirements
Install SymmetraTM in a temperature controlled, clean, dry, and protected indoor area that is free of conductive contaminants. The environment must have adequate airflow, and be free of corrosive fumes.
Environmental Condition | Acceptable Range |
|
|
Temperature | 32°F - 104°F (0°C - 40°C) |
|
|
Relative Humidity | 0 - 95% |
|
|
Elevation | 0 to 10,000 feet above mean sea level (0 to 3,048 m) |
|
|
Heat Output
Heat output of the SymmetraTM is significantly increased when batteries are charging. Battery recharge periods are relatively infrequent.
SymmetraTM Component | BTU Output | BTU Output | ||
(Batteries Charged) | (Batteries Charging) | |||
|
| |||
|
|
|
| |
| SYMINIF | 3,413 | 8,670 | |
North |
| |||
|
| |||
American |
|
|
| |
SYMSTRF |
|
| ||
Models | 6,826 | 15,640 | ||
| ||||
| ||||
|
|
| ||
|
|
|
| |
International | SYMINIFI | 2,321 | 7,578 | |
|
|
| ||
1:1 Models | SYMSTRFI |
|
| |
| 4,642 | 13,456 | ||
|
| |||
3:1 Model | SYMSTRF3I | |||
|
| |||
|
|
|
|
Short-Term Battery Module Storage Requirements
Battery modules must be temporarily stored until the electrical wiring is connected and the SymmetraTM is ready to be powered.
νBatteries should be stored at 0°F to 77°F
νStorage environment can be within 0 to 100% relative humidity ,
Caution!
νInstalling battery modules in a SymmetraTM that is not powered will discharge the batteries and could damage them permanently. Do not install battery modules into the SymmetraTM frame until after the electrical wiring connections have been made, and the system is ready to be powered.
Site Requirements - Page 3 | |
|