Appendix D

Specifications

Operation

System

Power Array having Hot-Swappable Modules which are Redundant, Scalable, Self-

 

diagnosing and Fault-tolerant.

 

 

Topology

On-Line, Triple Conversion with Power Factor Correction.

 

 

Power Capacity

4-16 kVA (2.8 - 11.2 kW)

 

 

Battery Type

Sealed Maintenance Free, Valve Regulated Lead Acid, (VRLA), 3-5 years life

 

 

Battery Charger

Automatic Float, Equalize High Frequency PWM charger.

 

 

Inverter

IGBT, High Frequency PWM, Microprocessor controlled.

 

 

Battery Recharge Time

< 3 Hours with standard supplied packs in the frame.

 

 

Extended Battery Option

Yes

 

 

Temperature

1°C - 40°C (32°F - 104°F)

 

 

Relative Humidity

0 - 95% non-condensing

 

 

Elevation

0 to 10,000 feet above mean sea level (0 to 3,048 m)

 

 

Input Specifications

Nominal Input Voltage

380 / 400 / 415 VAC, 50/60 Hz, 3 phase, 5 wire

 

 

Input Voltage Range

290 to 480 V AC (i.e. 400V +20%, -28% with Batteries charging)

 

 

Input Frequency Range

45-65 Hz.

 

 

Input Power Factor

0.95 @ Full Load

 

 

Input Inrush Current

< Full Load current at Nominal Voltage

 

 

Input Generator Sizing

1.5 x Frame Capacity - Feeder friendly, No Significant Oversizing, allow for Battery

 

Charging and System Efficiency

 

 

990-7172-001

Appendix D - Specifications - Page 1

 