Electrical Requirements

SymmetraTM

 

Voltage

Current

Overcurrent

Minimum

Wiring

Protection

Component

(VAC)

Full Load

Wire Size

 

(External)

 

 

 

 

 

 

 

 

Input

 

26A/Phase when

 

 

 

 

 

online, 50A on

 

 

 

 

with Bypass

 

60Amp 3-Pole

#8 AWG (10mm2)

 

 

 

L1 and L2 in

 

 

Transformer

380V, 400V,

 

 

 

 

bypass

 

 

 

 

 

or 415V

 

 

 

SYMSTRF3I

Input

26A/Phase when

 

 

 

 

 

 

International

 

without Bypass

 

online, 80A on

100Amp 3-Pole

#3 AWG (25mm2)

 

Transformer

 

L1 in bypass

 

 

3:1 Model

 

 

 

 

 

 

 

 

 

 

Output

220V, 230V,

80A

100Amp 1-Pole

#3 AWG (25mm2)

 

 

 

 

or 240V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bypass

Input

 

 

 

#8 AWG (10mm2)*

 

Balancing

 

Controlled by system frame.

 

 

Output

#3 AWG (25mm2)*

 

Transformer

 

 

 

 

 

 

 

 

 

 

* Install the bypass balancing transformer no further than 50' (15 m) from the SymmetraTM. If a greater distance is required, factor in voltage drop when selecting wire gauge.

EPO Switch Wiring (Required)

The SymmetraTM Power Array is to be connected to either a dry contact or 24Vdc Emergency Power Off (EPO) switch. The terminal connections for the EPO switch are physically isolated from the primary circuitry of the Power Array system.

EPO Specifications

The EPO circuit is considered a Class 2 and SELV circuit.

SELV is an acronym for “Safety Extra Low Voltage.” SELV is a common term in Europe and IEC standards. A SELV circuit is isolated from primary circuitry through an isolating transformer and designed so that under normal conditions, the voltage is limited to 42.4 Vpeak or 60 Vdc.

A Class 2 Circuit is a common term in North America and in UL and CSA standards. It is defined in the Canadian Electrical Code (C22.1, Section 16) and in the National Electrical Code (NFPA 70, Article 725).

SELV and Class 2 circuits must be isolated from all primary circuitry. Do not connect any circuit to the EPO terminal block unless it can be confirmed that the circuit is SELV or Class 2. If there is a question, use a contact closure switch. Use one of the following cable types to connect the SymmetraTM to the EPO switch:

CL2 - Class 2 cable for general purpose use.

CL2P - Plenum cable for use in ducts, plenums, and other space used for environmental air. CL2R - Riser cable for use in a vertical run in a shaft or from floor to floor.

CL2X - Limited Use cable for use in dwellings and for use in raceway.

For installation in Canada, the cable should be CSA Certified, type ELC (Extra-Low-Voltage Control Cable).

Page 2 - Electrical Installation

990-7166-001

 

Page 26