1.Remove the appropriate grill cover. The battery module bays are labeled on the center spine behind the grill covers.

2.Battery modules are designed with a “drop lock” that holds them securely in the frame. Slightly lift the front handle of the battery module, and pull it forward to the safety stop.

3.With one person on either side of the battery module, lift and remove the battery module from the frame. Note: The safety stop retaining flange passes through the notch in the frame as the battery module is removed.

4.To dispose of the battery module, return it to the appropriate service provider or directly to APC for recycling. Note: The battery module contains sealed, non-spillable lead acid batteries. These must be recycled or disposed of properly.

5.Install the replacement battery module.

Replacement Battery Module Verification

From the startup screen, press any key to open the top level menu screen. Follow the sequence below to ensure that the new battery module is recognized by the Power Array system and is functioning properly. (Status: OK).

Warning!

νThe 120V, 7.2 Ah battery module constitutes a risk of electrical shock and an energy hazard. High short circuit current through conductive materials could cause severe burns. Before handling battery mod- ules, remove conductive jewelry such as chains, wrist watches and rings.

νBattery modules weigh approx. 60 lb (27 kg). Two people are required to handle battery modules.

990-7171-001