Electrical Requirements - Input/Output

SymmetraTM

 

Voltage

Current

Overcurrent

Minimum

Wiring

Protection

Component

(VAC)

Full Load

Wire Size

 

(External)

 

 

 

 

 

 

 

 

Input

208V

40A

50Amp 1-Pole

 

 

 

 

 

 

 

SYMINIF

240V

35A

#8 AWG (10mm2)

 

 

 

 

 

 

 

 

Output

120V/240V

40A

50Amp 2-Pole

 

 

 

 

 

 

 

 

 

 

120V/208V/240V

50Amp 3-Pole

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

208V

40A

50Amp 1-Pole

 

 

 

 

 

 

 

 

240V

35A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120V/240V

 

50Amp 2-Pole

 

 

SYMINIF-PD

 

 

 

 

#8 AWG (10mm2)

 

 

 

 

Overcurrent

 

 

Output

 

40A

protection is built

 

 

 

120V/208V/240V

into the power

 

 

 

 

 

 

North

 

 

 

 

distribution panel

 

 

 

 

 

for all output.

 

American

 

 

 

 

 

 

 

 

 

 

 

 

 

208V

80A

 

 

Models

 

Input

100Amp 1-Pole

 

 

 

 

 

SYMSTRF

240V

70A

#3 AWG (25mm2)

 

 

 

 

 

 

 

 

 

Output

120V/240V

80A

100Amp 2-Pole

 

 

 

 

 

 

 

 

 

 

120V/208V/240V

100Amp 3-Pole

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

208V

80A

100Amp 1-Pole

 

 

 

 

 

 

 

 

240V

70A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120V/240V

 

100Amp 2-Pole

 

 

SYMSTRF-PD

 

 

 

 

#3 AWG (25mm2)

 

 

 

 

Overcurrent

 

 

Output

 

80A

protection is built

 

 

 

120V/208V/240V

into the power

 

 

 

 

 

 

 

 

 

 

 

distribution panel

 

 

 

 

 

 

for all output.

 

 

 

 

 

 

 

 

 

SYMINIFI

Input

220V,

40A

50Amp 1-Pole

#8 AWG (10mm2)

 

 

International

Output

230V or 240V

 

 

 

 

 

 

 

 

 

1:1 Models

SYMSTRFI

Input

220V,

80A

100Amp 1-Pole

#3 AWG (25mm2)

 

Output

230V or 240V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

 

26A/Phase

 

 

 

 

 

when online,

 

 

 

 

with Bypass

 

60Amp 3-Pole

#8 AWG (10mm2)

 

 

 

50A on L1 and

 

 

Transformer

 

 

 

 

 

380V,

L2 in bypass

 

 

 

 

 

 

 

 

SYMSTRF3I

Input

400V or 415V

26A/Phase

 

 

International

 

 

when online,

100Amp 3-Pole

#3 AWG (25mm2)

 

without Bypass

 

 

 

 

 

 

 

3:1 Model

 

Transformer

 

80A on L1

 

 

 

 

in bypass

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

220V, 230V or 240V

80A

100Amp 1-Pole

#3 AWG (25mm2)

 

 

 

 

 

 

 

 

Bypass

Input

Controlled by system frame.

#8 AWG (10mm2)*

 

Balancing

 

 

 

Output

#3 AWG (25mm2)*

 

Transformer

 

 

 

*Install the bypass balancing transformer no further than 50' (15 m) from the SymmetraTM. If a greater distance is required, factor in voltage drop when selecting wire gauge.

Page 4 - Site Requirements