American Power Conversion SYMSTRF3I PowerView Meaning Corrective Action Message, General

Models: SYMSTRF3I

1 68
Download 68 pages 8.33 Kb
Page 57
Image 57

 

PowerView

Meaning

Corrective Action

 

Message

 

 

 

 

 

 

 

General

Fault, Internal Temp exceeded

The temperature of one or more

Replace the overheated modules. Refer

Fault

normal limits

battery modules is too hot.

to Appendix C for module replacement

 

 

procedures.

 

 

 

 

 

 

 

 

Input circuit breaker tripped

The input circuit breaker on the

Option #1: If this occurs in conjunction

 

open

SymmetraTM has tripped.

with an overload condition, decrease the

 

 

Input voltage is disconnected to the

load and reset the breaker.

 

 

SymmetraTM.

Option #1: If no overload condition

 

 

 

exists, reset breaker. If it trips again, call

 

 

 

your contract service provider, or APC

 

 

 

Technical Support. (See inside front

 

 

 

cover.)

 

 

 

 

 

System level fan failed

A cooling fan in the SymmetraTM

Call your contract service provider, or

 

 

frame has failed.

APC Technical Support. (See inside front

 

 

 

cover.)

 

 

 

 

 

The Redundant Intelligence

The main intelligence module has

Replace the intelligence module. Refer to

 

Module is in control

failed, and the RIM is functioning as

Appendix C for module replacement

 

 

the primary intelligence module.

procedures.

 

 

 

 

 

IIC inter-module

The communications between the

Call your contract service provider, or

 

communications failed.

MIM and at least one other module

APC Technical Support. (See inside front

 

 

has failed.

cover.)

 

 

 

 

990-7170-001

Appendix B - Troubleshooting - Page 5

 

Page 57
Image 57
American Power Conversion SYMSTRF3I user manual PowerView Meaning Corrective Action Message, General