νDo not dispose of batteries or battery modules in a fire. The batteries may explode. Return all battery modules to APC or to an appropriate recycling center.

νDo not open or mutilate battery modules or batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.

νBattery modules are heavy (60 lb). Two people are required to handle battery modules.

νThis product is intended for installation in a temperature controlled, clean, dry, indoor area that is free of conductive contaminants. (0° to 40° C.)

νThis product must be connected to an Emergency Power Off (EPO) switch.

νTotal Power Off Procedure

Remove all power from the SymmetraTM before opening any of the wiring panels:

1.Set system enable switch to the “stand by” position.

2.Set input circuit breaker to the “stand by” position.

3.Remove all battery modules from the Power Array.

4.If an extended run battery cabinet is connected to the SymmetraTM, disconnect the cabinet by removing the power cable from the bottom rear connector of the SymmetraTM.

5.Disconnect the utility power source circuit breaker. Label it with a safety warning tag.

Radio Frequency Interference

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules and the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

Shielded cables must be used with this unit to ensure compliance with the Class A FCC limits.

Operation Symbols

“On Position”

Indicates that a switch or current protection device is in the “on” position. The

 

system enable switch, maintenance bypass switch and the input circuit breaker

 

can be placed in the “on” position.

“Off Position”

“Stand By Position”

Indicates that a switch is in the “off” position. The maintenance bypass switch is the only switch that can be placed in the “off” position.

Indicates that a switch or current protection device is in the “stand by” position. The system enable switch, and the input and output circuit breakers can be placed in the “stand by” position.

Page 2 - Safety Information

990-7162-001

 

Page 6
Image 6
American Power Conversion SYMSTRF3I user manual Radio Frequency Interference, Operation Symbols