PowerView

Meaning

Corrective Action

 

Message

 

 

 

 

 

 

 

General

# of batteries increased.

At least one battery module has been

No corrective action necessary.

Status

added to the system.

 

 

 

 

 

 

 

# of batteries decreased.

At least one battery module has been

No corrective action necessary.

 

removed from the system.

 

 

 

 

 

 

 

 

# of Pwr Modules increased.

At least one power module has been

No corrective action necessary.

 

added to the system.

 

 

 

 

 

 

 

 

# of Pwr Modules decreased.

At least one power module has been

No corrective action necessary.

 

removed from the system.

 

 

 

 

 

 

 

 

Intelligence Module inserted.

A MIM has been installed into the

No corrective action necessary.

 

SymmetraTM .

 

 

 

 

 

 

 

 

Intelligence Module removed

A MIM has been removed from the

No corrective action necessary.

 

SymmetraTM .

 

 

 

 

 

 

 

 

Redundant Intelligence

A RIM has been installed into the

No corrective action necessary.

 

Module inserted.

SymmetraTM .

 

 

 

 

 

 

 

Redundant Intelligence

A RIM has been removed from the

No corrective action necessary.

 

Module removed.

SymmetraTM .

 

 

 

 

 

 

 

# of External Battery Cabinets

At least one external battery cabinet has

No corrective action necessary.

 

increased.

been connected to the frame.

 

 

 

 

 

 

 

# of External Battery Cabinets

At least one external battery cabinet has

No corrective action necessary.

 

decreased.

been disconnected from the SymmetraTM.

 

 

 

 

 

 

 

 

A loss of power module redundancy

 

 

Redundancy Restored

occurred, and has been restored. Either

No corrective action necessary.

 

additional modules have been installed,

 

 

 

 

 

or the load has been reduced.

 

 

 

 

 

 

 

The load had exceeded the load alarm

 

 

Load is No Longer above Alarm

threshold. The situation has been

 

 

corrected either because the load

No corrective action necessary.

 

Threshold

 

decreased, or the threshold was

 

 

 

 

 

 

increased.

 

 

 

 

 

 

 

The system runtime had dropped below

 

 

 

the configured minimum, and has been

 

 

Min Runtime restored.

restored. Either additional battery

No corrective action necessary.

 

modules were installed, the existing

 

 

 

 

 

battery modules recharged, the load was

 

 

 

reduced, or the threshold was raised.

 

 

 

 

 

Page 2 - Troubleshooting - Appendix B

990-7170-001

 

Page 54