Main Intelligence Module Replacement

1.Remove the grill cover from the top level of the Power Array.

The intelligence module resides under the redundant intelligence module in the upper right corner of the frame. Note: If a functioning RIM is installed, it will provide limited control of the SymmetraTM until the replacement MIM is installed. If a functioning RIM is not installed, either the SymmetraTM must be placed in manual bypass mode or the load equipment must be switched off. To place the SymmetraTM in manual bypass, switch the maintenance bypass switch to the “on” position.

Important: When the SymmetraTM is in bypass mode, the load equipment is unprotected from power failure.

2.Use a flathead screwdriver to release the flip latch.

3.Unscrew and release the retaining screws.

4.Slide the MIM out of the frame.

5.Slide the replacement MIM into the frame. If SymmetraTM was placed in manual bypass in step 1 above, return to normal operation by switching the maintenance bypass switch back to the “off” position.

Replacement MIM Verification

From the startup screen, press any key to open the top level menu screen. Follow the sequence in below to ensure that the replacement MIM is functioning properly. (Status: On & OK).

Redundant Intelligence Module Replacement

1.Remove the grill cover from the top level of the Power Array.

The redundant intelligence module resides above the intelligence module in the upper right corner of the frame. Note. A RIM can only be replaced if a functioning MIM is installed or the load equipment is switched off.

2.Use a flathead screwdriver to release the flip latch.

3.Unscrew and release the retaining screws.

4.Slide the RIM out of the frame.

5.Slide the replacement RIM into the frame.

Replacement RIM Verification

From the startup screen, press any key to open the top level menu screen. Follow the sequence in below to ensure that the replacement RIM is functioning properly. (Status: On & OK).

990-7171-001

Appendix C - Module Replacement - Page 5

 

Page 63